84 Application macros
Torque control macro
This macro is used in applications in which torque control of the motor is required.
These are typically tension applications, where a particular tension needs to be
maintained in the mechanical system.
Torque reference is given through analog input AI2, typically as a current signal in the
range of 0…20 mA (corresponding to 0…100% of rated motor torque).
The start/stop signal is connected to digital input DI1. The direction is determined by
DI2. Through digital input DI3, it is possible to select speed control (EXT1) instead of
torque control (EXT2).Speed control can be used for commissioning the system and
checking the motor direction.
It is also possible to change the control to local (control panel or PC tool) by pressing
the Loc/Rem key. By default, the local reference is speed; if a torque reference is
required, the value of parameter
should be changed to
.
A constant speed (by default, 300 rpm) can be activated through DI4. DI5 switches
between acceleration/deceleration time sets 1 and 2. The acceleration and
deceleration times, as well as ramp shapes, are defined by parameters
Default parameter settings for the Torque control macro
Below is a listing of default parameter values that differ from those listed for the
Factory macro in
).
Parameter
Torque control macro
default
No.
Name
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...