86 Application macros
Sequential control macro
The Sequential control macro is suited for speed control applications in which a
speed reference, multiple constant speeds, and two acceleration and deceleration
ramps can be used.
Only EXT1 is used in this macro.
The macro offers seven preset constant speeds which can be activated by digital
inputs DI4…DI6 (see parameter
). An external speed
reference can be given through analog input AI1. The reference is active only when
no constant speed is activated (digital inputs DI4…DI6 are all off). Operational
commands can also be given from the control panel.
The start/stop commands are given through digital input DI1; running direction is
determined by DI2.
Two acceleration/deceleration ramps are selectable through DI3. The acceleration
and deceleration times, as well as ramp shapes, are defined by parameters
Operation diagram
The figure below shows an example of the use of the macro.
Stop along deceleration
ramp
Speed
Time
Accel1
Accel1
Accel2
Decel2
Start/Stop
Accel1/Decel1
Speed 1
Speed 2
Accel2/Decel2
Speed 3
Speed 1
Speed 2
Speed 3
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...