Selection of constant speeds
By default, constant speeds 1…7 are selected using digital inputs DI4…DI6 as
follows:
Default parameter settings for the Sequential control macro
Below is a listing of default parameter values that differ from those listed for the
Factory macro in
).
Parameter
Sequential control macro
default
No.
Name
01b (Bit 0 = Packed)
600.00 rpm
900.00 rpm
1200.00 rpm
1500.00 rpm
2400.00 rpm
3000.00 rpm
25.06 Acc comp derivation time
0.12 s
DI4
DI5
DI6
Constant speed active
0
0
0
None (External speed
reference used)
1
0
0
Constant speed 1
0
1
0
Constant speed 2
1
1
0
Constant speed 3
0
0
1
Constant speed 4
1
0
1
Constant speed 5
0
1
1
Constant speed 6
1
1
1
Constant speed 7