102 Parameters
Running time of the drive cooling fan. Can be reset from the
control panel by keeping Reset depressed for over 3 seconds.
-
0…65535 d
Cooling fan run-time counter.
1 = 1 d
500-microsecond ticks elapsed since the last boot of the
control unit.
-
0…4294967295
500-microsecond ticks since last boot.
1 = 1
Estimated drive temperature in percent of fault limit. The
actual trip temperature varies according to the type of the
drive.
0.0% = 0 °C
94% approx. = Warning limit
100.0% = Fault limit
-
-40.0 … 160.0%
Drive temperature in percent.
1 = 1%
Diagnostic word 3.
-
0000h…FFFFh
Diagnostic word 3.
1 = 1
06
Drive control and status words.
The main control word of the drive. This parameter shows the
control signals as received from the selected sources (such as
digital inputs, the fieldbus interfaces and the application
program).
The bit assignments of the word are as described on page
. The related status word and state diagram are presented
Notes:
• Bits 12…15 can be used to carry additional control data,
and used as a signal source by any binary-source selector
parameter. Bit 10 must be active for bits 12…15 to update.
• In fieldbus control, this parameter value is not exactly the
same as the control word that the drive receives from the
PLC. See parameter
This parameter is read-only.
-
0000h…FFFFh
Main control word.
1 = 1
The drive control word received from the application program
(if any). The bit assignments are described on page
This parameter is read-only.
-
0000h…FFFFh
Application program control word.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Value
0…10
Reserved
11
Fan command
1 = Drive fan is rotating above idle speed
counter
1 = Drive fan service counter has reached its limit
13…15 Reserved
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...