182 Parameters
When enabled by parameter
, adds
an additional step to the torque reference.
A second torque step can be added using pointer parameters
The two torque steps work independently of each other, and
are summed up to calculate the total torque step.
Note:
For safety reasons, the torque steps are not applied
when an emergency stop is active.
WARNING!
If the total torque step exceeds the limits
, a ramp stop may be
impossible. Make sure the torque step is reduced or disabled
when a ramp stop is required.
0.0%
-300.0 … 300.0%
Torque step.
See par.
Enables/disables the torque step defined by parameter
Disable
Torque step disabled.
0
Enable
Torque step enabled.
1
Selects a source that enables/disables the torque step
defined by parameter
.
See also parameter
1 = Torque step enabled.
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0).
10
DIO2
Digital input/output DIO2 (
, bit 1).
11
-
Selects the source of the torque step enabled by
Zero
None.
0
AI1 scaled
(see page
).
1
AI2 scaled
(see page
).
2
FB A ref1
(see page
4
FB A ref2
(see page
5
EFB ref1
(see page
).
8
EFB ref2
(see page
).
9
DDCS ctrl ref1
).
10
DDCS ctrl ref2
).
11
M/F reference 1
(see page
12
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...