Parameters 233
Displays the percentage of samples recorded by amplitude
logger 2 that fall between 60 and 70%.
0.00%
0.00 … 100.00%
Amplitude logger 2 samples between 60 and 70%.
1 = 1%
Displays the percentage of samples recorded by amplitude
logger 2 that fall between 70 and 80%.
0.00%
0.00 … 100.00%
Amplitude logger 2 samples between 70 and 80%.
1 = 1%
Displays the percentage of samples recorded by amplitude
logger 2 that fall between 80 and 90%.
0.00%
0.00 … 100.00%
Amplitude logger 2 samples between 80 and 90%.
1 = 1%
Displays the percentage of samples recorded by amplitude
logger 2 that exceed 90%.
0.00%
0.00 … 100.00%
Amplitude logger 2 samples over 90%.
1 = 1%
Displays the date on which amplitude logger 2 was last reset. -
-
Last reset date of amplitude logger 2.
-
Displays the time at which amplitude logger 2 was last reset.
-
-
Last reset time of amplitude logger 2.
-
37
Configuration of mechanical brake control.
See also section
Displays the mechanical brake control status word.
This parameter is read-only.
-
0000h…FFFFh
Mechanical brake control status word.
1 = 1
Displays the torque (in percent) at the instant of the previous
brake close command.
This value can be used as a reference for the brake open
torque. See parameters
and
.
A filtering time for this value can be defined using
44.21
Filter
time brake torque memory
.
-
-1600.0 … 1600.0% Torque at brake closure.
See par.
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Information
0
Open command
Close/open command to brake actuator (0 = close, 1 = open).
Connect this bit to desired output.
1
Opening torque
request
1 = Opening torque requested from drive logic
2
Hold stopped
request
1 = Hold requested from drive logic
3
Ramp to stopped
1 = Ramping down to zero speed requested from drive logic
4
Enabled
1 = Brake control is enabled
5
Closed
state
6
Opening
state
7
Open
state
8
Closing
state
9…15
Reserved
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...