88 Application macros
Default control connections for the Sequential control macro
Fault
XPOW
External power input
1
+24VI
24 V DC, 2
A
2
GND
XAI
Reference voltage and analog inputs
1
+VREF
10 V DC,
R
L
1…10 kohm
2
-VREF
-10 V DC,
R
L
1…10 kohm
3
AGND
Ground
4
AI1+
Speed reference
0(2)…10 V,
R
in
> 200 kohm
5
AI1-
6
AI2+
By default, not in use.
0(4)…20 mA,
R
in
= 100 ohm
7
AI2-
XAO
Analog outputs
1
AO1
Motor speed rpm
0…20 mA,
R
L
< 500 ohm
2
AGND
3
AO2
Motor current
0…20 mA,
R
L
< 500 ohm
4
AGND
XD2D
Drive-to-drive link
1
B
Master/follower, drive-to-drive or embedded fieldbus
interface connection
2
A
3
BGND
XRO1, XRO2, XRO3
Relay outputs
1
NC
250 V AC / 30 V DC
2 A
2
COM
3
NO
1
NC
250 V AC / 30 V DC
2 A
2
COM
3
NO
1
NC
250 V AC / 30 V DC
2 A
2
COM
3
NO
XD24
Digital interlock
1
DIIL
Run enable
2
+24VD
+24 V DC 200 mA
3
DICOM
Digital input ground
4
+24VD
+24 V DC 200 mA
5
DIOGND Digital input/output ground
XDIO
Digital input/outputs
1
DIO1
:
2
DIO2
: Used for R8i main fan fault
monitoring(Connected to the auxiliary contact of fan
control circuit controlled by end user).
XDI
Digital inputs
1
DI1
Stop (0) / Start (1)
2
DI2
Forward (0) / Reverse (1)
3
DI3
Acc/Dec time set 1 (0) / set 2 (1)
4
DI4
Constant speed selection (see page
)
5
DI5
6
DI6
XDIL
Drive interlocked circuits must be closed for the drive to start. See
Hardware manual
of drive.
X13
Control panel connection
X205
Memory unit connection
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...