4 EN – Quick installation guide
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN
Install the drive on the wall
See figures
and
on page
.
Check the insulation of the input and motor cables and the
motor
Check the insulation of the input cable according to local regulations before
connecting it to the drive.
Check the insulation of the motor cable and motor when the cable is disconnected
from the drive, see figure
on page
. Measure the insulation resistance between
each phase conductor and the Protective Earth conductor using a measuring voltage
of 1000 V DC. The insulation resistance of an ABB motor must exceed 100 Mohm
(reference value at 25 °C or 77 °F). For the insulation resistance of other motors,
please consult the manufacturer’s instructions.
Note:
Moisture inside the motor
casing will reduce the insulation resistance. If moisture is suspected, dry the motor
and repeat the measurement.
Connect the power cables
,
and
. Use symmetrical shielded cable for the motor cabling.
1. Remove the front cover. IP21 units: Release the retaining clip with a screwdriver
(a) and lift the cover from the bottom outwards (b). Remove the cable entry box
cover by undoing the mounting screw.
2. Attach the residual voltage warning sticker in the local language next to the
control board top.
3. Remove the shroud on the power cable terminals by releasing the clips and lifting
the shroud up from the sides with a screwdriver (a). Knock out holes for the
cables to be installed (b).
4. Cut adequate holes into the rubber grommets. Slide the grommets onto the
cables. Prepare the cable ends. Slide the cables through the holes of the bottom
plate and attach the grommets to the holes.
5. Ground the cable shields 360 degrees under the grounding clamps.
6. Connect the twisted cable shields to the grounding terminals.
7. Connect the conductors of the input and motor cables. Tighten the screws.
8. Install the EMC shroud separating the input and output cabling if not installed yet.
9. Units with D150: Connect the conductors of the brake resistor cable to the
R+ and R- terminals.
10. Reinstall the shroud on the power terminals.
11. Secure the cables outside the unit mechanically.
Summary of Contents for ACS880-01-046A-2
Page 22: ...22 DE Kurzanleitung für die Installation DE DA DE DE FI FR IT NL PT RU SV TR CN ...
Page 28: ...28 ES Guía rápida de instalación ES DA DE ES ES FR IT NL PT RU SV TR CN ...
Page 38: ...38 FR Guide d installation FR DA DE ES FI FR FR NL PT RU SV TR CN ...
Page 44: ...44 IT Guida rapida all installazione IT DA DE ES FI FR IT IT PT RU SV TR CN ...
Page 50: ...50 NL Beknopte installatiegids NL DA DE ES FI FR IT NL NL RU SV TR CN ...
Page 56: ...56 PL Skrócona instrukcja montażu PL DA DE ES FI FR IT NL PT PL PL TR CN ...
Page 62: ...62 PT Guia rápido de instalação PT DA DE ES FI FR IT NL PT PT PT TR CN ...
Page 68: ...68 RU Руководство по быстрому монтажу EN EN DA DE ES FI FR IT NL PT RU RU TR CN ...