Electrical installation 101
Notes:
1)
Current [0(4)…20 mA,
R
in
> 100 ohm] or voltage [ 0(2)…10 V,
R
in
> 200 kohm] input selected
with jumper J1. Change of setting requires reboot of control unit.
2)
Current [0(4)…20 mA,
R
in
> 100 ohm] or voltage [ 0(2)…10 V,
R
in
> 200 kohm] input selected
with jumper J2. Change of setting requires reboot of control unit.
3)
Total load capacity of these outputs is 4.8 W (200 mA / 24 V) minus the power taken by DIO1
and DIO2.
4)
0 = open, 1 = closed
Further information on the usage of the connectors and jumpers is given in the sections below.
See also section
Control unit (ZCU-12) connection data
on page
Jumpers and switches
DI4 Ramp times according to
0
Parameters 23.12 and 23.13
1
Parameters 23.14 and 23.15
Jumper/
Switch
Description
Positions
J1
(AI1)
Determines whether analog input AI1 is used
as a current or voltage input.
Current (I)
Voltage (U)
J2
(AI2)
Determines whether analog input AI2 is used
as a current or voltage input.
Current (I)
Voltage (U)
J3
Drive-to-drive link termination. Must be set to
terminated position when the drive is the last
unit on the link.
Bus is terminated.
Bus is not terminated.
J6
Common digital input ground selection switch.
Determines whether DICOM is separated from
DIOGND (ie, common reference for digital
inputs floats). See
on page
DICOM and DIOGND
connected (default).
DICOM and DIOGND
separated.
ACS880-01 HW.book Page 101 Monday, July 1, 2013 4:51 PM
Summary of Contents for ACS880-01 Series
Page 4: ...ACS880 01 HW book Page 4 Monday July 1 2013 4 51 PM...
Page 12: ...12 ACS880 01 HW book Page 12 Monday July 1 2013 4 51 PM...
Page 20: ...20 Safety instructions ACS880 01 HW book Page 20 Monday July 1 2013 4 51 PM...
Page 26: ...26 Introduction to the manual ACS880 01 HW book Page 26 Monday July 1 2013 4 51 PM...
Page 80: ...80 Planning the electrical installation ACS880 01 HW book Page 80 Monday July 1 2013 4 51 PM...
Page 96: ...96 Electrical installation 8b R8 R9 ACS880 01 HW book Page 96 Monday July 1 2013 4 51 PM...
Page 98: ...98 Electrical installation 16 13 R8 R9 ACS880 01 HW book Page 98 Monday July 1 2013 4 51 PM...
Page 118: ...118 Start up ACS880 01 HW book Page 118 Monday July 1 2013 4 51 PM...
Page 120: ...120 Fault tracing ACS880 01 HW book Page 120 Monday July 1 2013 4 51 PM...
Page 131: ...Maintenance 131 3 4 5 3 ACS880 01 HW book Page 131 Monday July 1 2013 4 51 PM...
Page 172: ...172 Technical data ACS880 01 HW book Page 172 Monday July 1 2013 4 51 PM...
Page 196: ...196 Dimension drawings ACS880 01 HW book Page 196 Monday July 1 2013 4 51 PM...
Page 209: ...Safe Torque off function 209 Certificate ACS880 01 HW book Page 209 Monday July 1 2013 4 51 PM...
Page 210: ...210 Safe Torque off function ACS880 01 HW book Page 210 Monday July 1 2013 4 51 PM...
Page 220: ...220 Resistor braking ACS880 01 HW book Page 220 Monday July 1 2013 4 51 PM...