104 Technical data
Ratings
Unit type
ACS880-
1607-…
Consists of
module
type
ACS880-
104-…
Frame
No-overload use
I
1
I
2
P
contmax
P
contmax
I
max
output
S
N
I
p2p
f
sw
out
A (DC) A (DC)
kW
hp
A (DC)
kVA
A
Hz
U
N
= 400 V
0600A-3
0640A-3
R8i
600
600
305
410
900
305
22
12000
0900A-3
0900A-3
R8i
900
900
458
614
1350
458
33
12000
1200A-3
0640A-3
2×R8i
1200
1200
611
819
1800
611
11
24000
1800A-3
0900A-3
2×R8i
1800
1800
916
1229
2700
916
16
24000
U
N
= 500 V
0600A-5
0590A-5
R8i
600
600
382
512
900
382
27
12000
0900A-5
0810A-5
R8i
900
900
573
768
1350
573
41
12000
1200A-5
0590A-5
2×R8i
1200
1200
764
1024
1800
764
14
24000
1800A-5
0810A-5
2×R8i
1800
1800
1146
1536
2700
1146
20
24000
U
N
= 690 V
0400A-7
0410A-7
R8i
400
400
351
471
600
351
38
12000
0600A-7
0600A-7
R8i
600
600
527
707
900
527
56
12000
0800A-7
0410A-7
2×R8i
800
800
703
942
1200
703
19
24000
1200A-7
0600A-7
2×R8i
1200
1200
1054
1413
1800
1054
28
24000
3AXD00000601909
Unit type
ACS880-
1607-…
Consists of
module
type
ACS880-
104-…
Frame
High-overload use
Heavy-duty use
I
f
ast
P
f
ast
I
Hd
P
Hd
A
kW
A
kW
U
N
= 400 V
0600A-3
0640A-3
R8i
450
229
510
260
0900A-3
0900A-3
R8i
675
343
765
389
1200A-3
0640A-3
2×R8i
899
458
1020
519
1800A-3
0900A-3
2×R8i
1349
687
1529
779
U
N
= 500 V
0600A-5
0590A-5
R8i
450
286
510
324
0900A-5
0810A-5
R8i
675
429
765
487
1200A-5
0590A-5
2×R8i
899
572
1020
649
1800A-5
0810A-5
2×R8i
1349
859
1529
973
U
N
= 690 V
0400A-7
0410A-7
R8i
300
263
340
298
0600A-7
0600A-7
R8i
450
395
510
448
0800A-7
0410A-7
2×R8i
600
527
680
597
1200A-7
0600A-7
2×R8i
899
790
1020
895
3AXD00000601909
Summary of Contents for ACS880-1607
Page 1: ...ABB industrial drives Hardware manual ACS880 1607 DC DC converter units ...
Page 4: ......
Page 12: ...12 Introduction to the manual ...
Page 34: ...34 Mechanical installation ...
Page 40: ...40 Guidelines for planning electrical installation ...
Page 52: ...52 Electrical installation ...
Page 68: ...68 Start up ...
Page 80: ...80 Maintenance 7 3 4 5 6 ...
Page 82: ...82 Maintenance 3 4 5 6 7 8 9 9 ...
Page 85: ...Maintenance 85 12 Install and tighten the two screws 10 11 12 ...
Page 92: ...92 Maintenance 3 6 4 5 4 7a 7b 7b ...
Page 93: ...Maintenance 93 9 8 8 10 11 ...
Page 96: ...96 Maintenance 4 8 6 7 5 3 ...
Page 97: ...Maintenance 97 9 ...
Page 118: ...118 Dimensions Dimension drawings Frame 1 R8i bottom cable entry ...
Page 119: ...Dimensions 119 Frame 1 R8i top cable entry ...
Page 122: ...www abb com drives www abb com drivespartners 3AXD50000023644 Rev B EN 2017 01 30 Contact us ...