112 Technical data
Control accuracy
–
Current and voltage control
performance data
Control unit connection data
See chapter
on page
Input power (DC bus) connection
Voltage (
U
1
)
ACS880-104-xxxxx-3 = DC voltage corresponding AC input voltages
3
380…415 V. This is indicated in the type designation label as typical input
voltage level 566 V DC.
ACS880-104-xxxxx-5 = DC voltage corresponding AC input voltages
3
380…500 V. This is indicated in the type designation label as typical input
voltage levels 566 / 679 / 707 V DC.
ACS880-104-xxxxx-7 = DC voltage corresponding AC input voltages
3
525…690 V. This is indicated in the type designation label as typical input
voltage levels 742 / 849 / 976 (849 UL/CSA) V DC.
Output power (energy storage) connection
Voltage (
U
2
)
ACS880-104-xxxxx-3 = Maximum output voltage 50 V…95% of
U
DC
(Drive DC
voltage in the DC bus).This is indicated in the type designation label as typical
output voltage range 50…509 V DC.
Recommended output voltage 150 V…80% of
U
DC.
ACS880-104-xxxxx-5 = Maximum output voltage 50 V…95% of
U
DC
(Drive DC
voltage in the DC bus). This is indicated in the type designation label as typical
output voltage range 50…509 / 611 / 636 V DC.
Recommended output voltage 150 V…80% of
U
DC.
.
ACS880-104-xxxxx-7 = Maximum output voltage 50 V…95% of
U
DC
(Drive DC
voltage in the DC bus). This is indicated in the type designation label as typical
output voltage range 50…668 / 764 / 878 V DC.
Recommended output voltage 150 V…80% of
U
DC.
Current
See section
Output terminals
See
.
Maximum energy storage
cable length
100 m (328 ft)
Current control dynamic
response
Step response time < 10 ms for a reference step 0% to 50% of the drive nominal
current)
Current control accuracy
(static)
Current error < 1% of the drive nominal current rating
For the DC current ripple, see
on page
ES voltage control
accuracy (static)
Voltage error < 1% of the drive nominal voltage (converter with the optional
BAMU voltage/current measurement unit, G442)
Note:
If the converter does not include the BAMU voltage/current measurement
unit, the voltage measurement accuracy depends on the customer’s
measurement device.
~
~
~
~
Summary of Contents for ACS880-1607
Page 1: ...ABB industrial drives Hardware manual ACS880 1607 DC DC converter units ...
Page 4: ......
Page 12: ...12 Introduction to the manual ...
Page 34: ...34 Mechanical installation ...
Page 40: ...40 Guidelines for planning electrical installation ...
Page 52: ...52 Electrical installation ...
Page 68: ...68 Start up ...
Page 80: ...80 Maintenance 7 3 4 5 6 ...
Page 82: ...82 Maintenance 3 4 5 6 7 8 9 9 ...
Page 85: ...Maintenance 85 12 Install and tighten the two screws 10 11 12 ...
Page 92: ...92 Maintenance 3 6 4 5 4 7a 7b 7b ...
Page 93: ...Maintenance 93 9 8 8 10 11 ...
Page 96: ...96 Maintenance 4 8 6 7 5 3 ...
Page 97: ...Maintenance 97 9 ...
Page 118: ...118 Dimensions Dimension drawings Frame 1 R8i bottom cable entry ...
Page 119: ...Dimensions 119 Frame 1 R8i top cable entry ...
Page 122: ...www abb com drives www abb com drivespartners 3AXD50000023644 Rev B EN 2017 01 30 Contact us ...