114 Technical data
Ambient conditions
The unit is to be used in a heated indoor controlled environment.
Operation
Storage
Transportation
Altitude above sea level
0…2000 m (0…6561.7 ft)
-
-
For altitudes over 2000 m (6561.7 ft), contact ABB.
Air temperature
0…+40 °C
(+32…+104 °F), no
condensation allowed
-40…+70 °C
(-104…+158 °F)
-40…+70 °C
(-104…+158 °F)
+40…+50 °C (+104…+122 °F) derating 1% /1 °C (+1.8 °F). For more information,
see
Relative humidity
Maximum 95%, no
condensation allowed
Maximum 95%, no
condensation allowed
Maximum 95%, no
condensation allowed
Contamination
IEC/EN 60721-3-3:2002:
Classification of
environmental conditions -
Part 3-3: Classification of
groups of environmental
parameters and their
severities Stationary use
of weather protected
locations
IEC 60721-3-1
IEC 60721-3-2
Chemical gases
Class 3C2
Class 1C2
Class 2C2
Solid particles
Class 3S1
Class 1S3 (packing must
support this, otherwise
1S2)
Class 2S2
No conductive dust
allowed.
Vibration
IEC/EN 61800-5-1
IEC 60068-2-6:2007,
EN 60068-2-6:2008
Environmental testing Part
2: Tests –Test Fc: Vibration
(sinusoidal)
IEC/EN 60721-3-3:2002
10…57 Hz: max.
0.075 mm amplitude
57…150 Hz: 1
g
Units with marine
construction (option
+C121):
Max. 1 mm (0.04 in.)
(5 … 13.2 Hz),
max. 0.7 g
(13.2 … 100 Hz)
sinusoidal)
IEC/EN 60721-3-1:1997
10…57 Hz: max.
0.075 mm amplitude
57…150 Hz: 1
g
IEC/EN 60721-3-2:1997
2…9 Hz: max. 3.5 mm
amplitude
9…200 Hz: 10 m/s
2
(32.8 ft/s
2
)
Shock
IEC 60068-2-27:2008
EN 60068-2-27:2009
Environmental testing - Part
2-27: Tests - Test Ea and
guidance: Shock
Not allowed
With packing max.
100 m/s
2
(330 ft./s
2
) 11 ms
With packing max.
100 m/s
2
(330 ft./s
2
) 11 ms
Summary of Contents for ACS880-1607
Page 1: ...ABB industrial drives Hardware manual ACS880 1607 DC DC converter units ...
Page 4: ......
Page 12: ...12 Introduction to the manual ...
Page 34: ...34 Mechanical installation ...
Page 40: ...40 Guidelines for planning electrical installation ...
Page 52: ...52 Electrical installation ...
Page 68: ...68 Start up ...
Page 80: ...80 Maintenance 7 3 4 5 6 ...
Page 82: ...82 Maintenance 3 4 5 6 7 8 9 9 ...
Page 85: ...Maintenance 85 12 Install and tighten the two screws 10 11 12 ...
Page 92: ...92 Maintenance 3 6 4 5 4 7a 7b 7b ...
Page 93: ...Maintenance 93 9 8 8 10 11 ...
Page 96: ...96 Maintenance 4 8 6 7 5 3 ...
Page 97: ...Maintenance 97 9 ...
Page 118: ...118 Dimensions Dimension drawings Frame 1 R8i bottom cable entry ...
Page 119: ...Dimensions 119 Frame 1 R8i top cable entry ...
Page 122: ...www abb com drives www abb com drivespartners 3AXD50000023644 Rev B EN 2017 01 30 Contact us ...