38 Guidelines for planning electrical installation
Selecting and routing the energy storage cables
Recommended cables
Use a 4-conductor shielded cable or 3-conductor shielded cable:
•
If you use a 4-conductor shielded cable, use 2 conductors for plus and 2 conductors
for minus and the shield for PE.
•
If you use a 3-conductor shielded cable, use 1 conductor for plus, 1 conductor for
minus and 1 conductor and the shield for PE.
Typical cable sizes
This table gives copper cable types. Cable sizing is based on max. 9 cables laid on a cable
ladder side by side, three ladder type trays one on top of the other, ambient temperature
30 °C, PVC insulation, surface temperature 70 °C and 90 °C (EN 60204-1 and IEC 60364-
5-2/2001). For other conditions, size the cables according to local safety regulations,
appropriate input voltage and the load current of the drive.
I
rms dim
is the dimensioning
current.
DC/DC converter unit
type
Frame
size
I
rms
dim
A
Cable data
3-conductor cable
4-conductor cable
PVC, T=70 °C,
copper cable
XLPE, T=90 °C,
copper cable
PVC, T=70 °C,
copper cable
XLPE, T=90 °C,
copper cable
mm
2
mm
2
mm
2
mm
2
U
N
= 400 V
ACS880-1607-0600A-3
R8i
720
3×(3×185+95)
2×(3×240+120)
2×(4×120+70)
1×(4×240+120)
ACS880-1607-0900A-3
R8i
1080
4×(3×240+120)
4×(3×150+70)
2×(4×240+120)
2×(4×185+95)
ACS880-1607-1200A-3 2×R8i 1440 2×(3×(3×185+95)) 2×(2×(3×240+120))
4×(4×120+70)
2×(4×240+120)
ACS880-1607-1800A-3 2×R8i 2160 2×(4×(3×240+120)) 2×(4×(3×150+70))
4×(4×240+120)
4×(4×185+95)
U
N
= 500 V
ACS880-1607-0600A-5
R8i
720
3×(3×185+95)
2×(3×240+120)
2×(4×120+70)
1×(4×240+120)
ACS880-1607-0900A-5
R8i
1080
4×(3×240+120)
4×(3×150+70)
2×(4×240+120)
2×(4×185+95)
ACS880-1607-1200A-5 2×R8i 1440 2×(3×(3×185+95)) 2×(2×(3×240+120))
4×(4×120+70)
2×(4×240+120)
ACS880-1607-1800A-5 2×R8i 2160 2×(4×(3×240+120)) 2×(3×(3×240+120))
4×(4×240+120)
4×(4×185+95)
U
N
= 690 V
ACS880-1607-0400A-7
R8i
480
2×(3×185+95)
2×(3×150+70)
1×(4×185+95)
1×(4×150+70)
ACS880-1607-0600A-7
R8i
720
3×(3×185+95)
2×(3×240+120)
2×(4×120+70)
1×(4×240+120)
ACS880-1607-0800A-7 2×R8i 960
4×(3×240+120))
4×(3×150+70)
2×(4×185+95)
2×(4×150+70)
ACS880-1607-1200A-7 2×R8i 1440 2×(3×(3×185+95)) 2×(2×(3×240+120))
4×(4×120+70)
2×(4×240+120)
3AXD00000601909
Summary of Contents for ACS880-1607
Page 1: ...ABB industrial drives Hardware manual ACS880 1607 DC DC converter units ...
Page 4: ......
Page 12: ...12 Introduction to the manual ...
Page 34: ...34 Mechanical installation ...
Page 40: ...40 Guidelines for planning electrical installation ...
Page 52: ...52 Electrical installation ...
Page 68: ...68 Start up ...
Page 80: ...80 Maintenance 7 3 4 5 6 ...
Page 82: ...82 Maintenance 3 4 5 6 7 8 9 9 ...
Page 85: ...Maintenance 85 12 Install and tighten the two screws 10 11 12 ...
Page 92: ...92 Maintenance 3 6 4 5 4 7a 7b 7b ...
Page 93: ...Maintenance 93 9 8 8 10 11 ...
Page 96: ...96 Maintenance 4 8 6 7 5 3 ...
Page 97: ...Maintenance 97 9 ...
Page 118: ...118 Dimensions Dimension drawings Frame 1 R8i bottom cable entry ...
Page 119: ...Dimensions 119 Frame 1 R8i top cable entry ...
Page 122: ...www abb com drives www abb com drivespartners 3AXD50000023644 Rev B EN 2017 01 30 Contact us ...