58 Control unit
Control unit connector data
Power supply
(XPOW)
Connector pitch 5 mm, wire size 2.5 mm
2
24 V (±10%) DC, 2 A
External power supply in. Two supplies can be connected to BCU
for redundancy.
Relay outputs RO1…RO3
(XRO1…XRO3)
Connector pitch 5 mm, wire size 2.5 mm
2
250 V AC / 30 V DC, 2 A
Protected by varistors
+24 V output
(XD24:2 and XD24:4)
Connector pitch 5 mm, wire size 2.5 mm
2
Total load capacity of these outputs is 4.8 W (200 mA / 24 V) minus
the power taken by DIO1 and DIO2.
Digital inputs DI1…DI6 (XDI:1…XDI:6)
Connector pitch 5 mm, wire size 2.5 mm
2
24 V logic levels: “0” < 5 V, “1” > 15 V
R
in
: 2.0 kohm
Input type: NPN/PNP (DI1…DI5), NPN (DI6)
Hardware filtering: 0.04 ms, digital filtering up to 8 ms
DI6 (XDI:6) can alternatively be used as an input for a PTC
thermistor.
“0” > 4 kohm, “1” < 1.5 kohm
I
max
: 15 mA (DI1…DI5), 5 mA (DI6)
Start interlock input DIIL
(XDI:7)
Connector pitch 5 mm, wire size 2.5 mm
2
24 V logic levels: “0” < 5 V, “1” > 15 V
R
in
: 2.0 kohm
Input type: NPN/PNP
Hardware filtering: 0.04 ms, digital filtering up to 8 ms
Digital inputs/outputs DIO1 and DIO2
(XDIO:1 and XDIO:2)
Input/output mode selection by
parameters.
DIO1 can be configured as a frequency
input (0…16 kHz with hardware filtering
of 4 microseconds) for 24 V level square
wave signal (sinusoidal or other wave
form cannot be used). DIO2 can be
configured as a 24 V level square wave
frequency output. See the firmware
manual of the converter unit
,
parameter
group 111.
Connector pitch 5 mm, wire size 2.5 mm
2
As inputs:
24 V logic levels: “0” < 5 V, “1” > 15 V
R
in
: 2.0 kohm
Filtering: 1 ms
As outputs:
Total output current from +24VD is limited to 200 mA
Reference voltage for analog inputs
+VREF and -VREF
(XAI:1 and XAI:2)
Connector pitch 5 mm, wire size 2.5 mm
2
10 V ±1% and –10 V ±1%,
R
load
1…10 kohm
Maximum output current: 10 mA
Analog inputs AI1 and AI2
(XAI:4 … XAI:7).
Current/voltage input mode selection by
switches.
Connector pitch 5 mm, wire size 2.5 mm
2
Current input: –20…20 mA,
R
in:
100 ohm
Voltage input: –10…10 V,
R
in
: 200 kohm
Differential inputs, common mode range ±30 V
Sampling interval per channel: 0.25 ms
Hardware filtering: 0.25 ms, adjustable digital filtering up to 8 ms
Resolution: 11 bit + sign bit
Inaccuracy: 1% of full scale range
R
L
DIOx
DIOGND
+24VD
Summary of Contents for ACS880-1607
Page 1: ...ABB industrial drives Hardware manual ACS880 1607 DC DC converter units ...
Page 4: ......
Page 12: ...12 Introduction to the manual ...
Page 34: ...34 Mechanical installation ...
Page 40: ...40 Guidelines for planning electrical installation ...
Page 52: ...52 Electrical installation ...
Page 68: ...68 Start up ...
Page 80: ...80 Maintenance 7 3 4 5 6 ...
Page 82: ...82 Maintenance 3 4 5 6 7 8 9 9 ...
Page 85: ...Maintenance 85 12 Install and tighten the two screws 10 11 12 ...
Page 92: ...92 Maintenance 3 6 4 5 4 7a 7b 7b ...
Page 93: ...Maintenance 93 9 8 8 10 11 ...
Page 96: ...96 Maintenance 4 8 6 7 5 3 ...
Page 97: ...Maintenance 97 9 ...
Page 118: ...118 Dimensions Dimension drawings Frame 1 R8i bottom cable entry ...
Page 119: ...Dimensions 119 Frame 1 R8i top cable entry ...
Page 122: ...www abb com drives www abb com drivespartners 3AXD50000023644 Rev B EN 2017 01 30 Contact us ...