52 Operation principle and hardware description
The customer connects PTC sensors to the thermistor relay, and the terminals of the
auxiliary relay of the normally open contact, for example, to
•
main breaker control circuit of the drive for opening the breaker in case of motor
overtemperature or
•
appropriate digital input of the drive for tripping the drive and generating a fault
message in case of motor overtemperature or
•
customer control circuit.
See also
•
firmware manual for parameter settings
•
Wiring the thermistor relay(s) (oL505 and +2L505)
on page
•
circuit diagrams delivered with the drive for the actual wiring.
Pt100 relays (o2L506, +3L506, +5L506, +8L506)
What the option contains
The standard Pt100 relay option includes two (+2L506), three (+3L506), five (+5L506) or
eight (+8L506) Pt100 temperature monitoring relays and an auxiliary relay wired to a
terminal block. Other numbers of Pt100 relays must be ordered as application engineered.
Description
A Pt100 relay is used for overtemperature supervision of motors equipped with Pt100
sensors. For example, three sensors measure the temperature of the motor windings and
two sensors the temperature of the bearings. The sensor resistance increases linearly as
the temperature rises. The relay releases at an adjustable wake-up level and indicates
motor overtemperature through its change-over contact.
The relay provides connection terminals for one Pt100 temperature sensor and terminals
of one normally open and one normally closed contact.
The customer connects Pt100 sensors to the Pt100 relays (one sensor per relay) and the
auxiliary relays of the normally open contacts of the Pt100 relays, for example, to
•
main breaker control circuit of the drive for opening the breaker in case of motor
overtemperature or
•
appropriate digital input of the drive for tripping the drive and generating a fault
message in case of motor overtemperature or
•
customer control circuit.
See also
•
firmware manual for parameter settings
•
Wiring the Pt100 relays (o2L506, +3L506, +5L506 and +8L506)
•
Pt100 relay alarm and trip limit setting instructions on page
•
circuit diagrams delivered with the drive for the actual wiring.
Summary of Contents for ACS880-17
Page 1: ...ABB industrial drives Hardware manual ACS880 37 drives ...
Page 3: ......
Page 4: ......
Page 6: ......
Page 16: ...16 ...
Page 30: ...30 Introduction to the manual ...
Page 70: ...70 Mechanical installation ...
Page 105: ...Electrical installation 105 4 5 3 6 7 ...
Page 107: ...Electrical installation 107 5 6 4 3 ...
Page 108: ...108 Electrical installation 7 8 8 ...
Page 109: ...Electrical installation 109 9 10 ...
Page 111: ...Electrical installation 111 2 360 grounding detail a b b 1 5 a 11 b a PE 10 7 5 6 8 ...
Page 117: ...Electrical installation 117 PE 11 8 4 9 11 ...
Page 134: ...134 Control units of the drive ...
Page 140: ...140 Start up ...
Page 142: ...142 Fault tracing ...
Page 154: ...154 Maintenance 4 5 6 7 8 6 10 10 ...
Page 162: ...162 Maintenance 5 6 3 4 7 ...
Page 163: ...Maintenance 163 6 8 7 11 10 9 ...
Page 167: ...Maintenance 167 3 4b 4a 4b 8 ...
Page 185: ...Technical data 185 Declaration of Conformity ...
Page 186: ...186 Technical data ...
Page 196: ...196 Dimensions Dimension drawing examples Frame 1 R8i 1 R8i ...
Page 197: ...Dimensions 197 Frame 1 R8i 1 R8i top cable entry exit H351 H353 ...
Page 198: ...198 Dimensions Frame 1 R8i 1 R8i with brake choppers and resistors D150 D151 ...
Page 199: ...Dimensions 199 Frame 1 R8i 1 R8i with sine output filter E206 ...
Page 200: ...200 Dimensions Frame 2 R8i 2 R8i eg ACS880 37 1110A 3 IP22 ...
Page 201: ...Dimensions 201 Frame 2 R8i 2 R8i eg ACS880 37 1210A 3 IP54 ...
Page 204: ...204 Dimensions Frame 2 R8i 2 R8i with main breaker F255 and top entry top exit H351 H353 1 2 ...
Page 205: ...Dimensions 205 Frame 2 R8i 2 R8i with main breaker F255 and top entry top exit H351 H353 2 2 ...
Page 206: ...206 Dimensions Frame 3 R8i 3 R8i 1 2 ...
Page 207: ...Dimensions 207 Frame 3 R8i 3 R8i 2 2 ...
Page 208: ...208 Dimensions Frame 3 R8i 3 R8i with common motor terminal cubicle H359 1 2 ...
Page 209: ...Dimensions 209 Frame 3 R8i 3 R8i with common motor terminal cubicle H359 2 2 ...
Page 217: ...Dimensions 217 Sine filter E206 cubicle 1000 mm top cable exit ...
Page 221: ...Dimensions 221 Cubicle width 400 mm top cable exit Cubicle width 600 mm bottom cable exit ...
Page 222: ...222 Dimensions Cubicle width 600 mm top cable exit ...
Page 234: ...234 The Safe torque off function ...
Page 244: ...www abb com drives www abb com drivespartners 3AXD50000020437 Rev A EN 2015 02 06 Contact us ...