Guidelines for planning the electrical installation 85
Residual current device compatibility
The drive is suitable to be used with residual current devices of Type B.
Note
: The EMC filter of the drive includes capacitors connected between the main circuit
and the frame. These capacitors and long motor cables increase the ground leakage
current and may cause fault current circuit breakers to function.
Implementing the emergency stop function
The drive can be equipped with a category 0 and 1 emergency stop function (option
+Q951, +Q952, +Q963, +Q964, +Q978 or +Q979). For safety reasons, install the
emergency stop devices at each operator control station and at other operating stations
where emergency stop may be needed.
Note
: Pressing the stop key
on the control panel of the drive, or turning the operating
switch of the drive from position “1” to “0” does not generate an emergency stop of the
motor or separate the drive from dangerous potential.
See the appropriate user’s manual for the wiring, start-up and operation instructions.
Implementing the Safe torque off function
See chapter
(page
Implementing the Prevention of unexpected start-up
function
The drive can be equipped with a Prevention of unexpected start-up (POUS) function
either with an FSO-xx safety functions module (Q950) or with a safety relay
(Q957). The POUS function enables short-time maintenance work (like cleaning)
on the non-electrical parts of the machinery without switching off and disconnecting the
drive.
See the appropriate user’s manual for the wiring, start-up and operation instructions.
Option
code
User’s manual
Manual code
(English)
+Q951 Emergency stop, stop category 0 (using main contactor/breaker)
3AUA0000119895
+Q952 Emergency stop, stop category 1 (using main contactor/breaker)
3AUA0000119896
+Q963 Emergency stop, stop category 0 (using Safe torque off)
3AUA0000119908
+Q964 Emergency stop, stop category 1 (using Safe torque off)
3AUA0000119909
+Q978 Emergency stop, stop category 0 or 1 (using main contactor/breaker and Safe
torque off)
3AUA0000145920
+Q979 Emergency stop, stop category 0 or 1 (using Safe torque off)
3AUA0000145921
Option
code
User’s manual
Manual code
(English)
+Q950 Prevention of unexpected start-up, with FSO-xx safety functions module
3AUA0000145922
+Q957 Prevention of unexpected start-up, with safety relay
3AUA0000119910
Summary of Contents for ACS880-17
Page 1: ...ABB industrial drives Hardware manual ACS880 37 drives ...
Page 3: ......
Page 4: ......
Page 6: ......
Page 16: ...16 ...
Page 30: ...30 Introduction to the manual ...
Page 70: ...70 Mechanical installation ...
Page 105: ...Electrical installation 105 4 5 3 6 7 ...
Page 107: ...Electrical installation 107 5 6 4 3 ...
Page 108: ...108 Electrical installation 7 8 8 ...
Page 109: ...Electrical installation 109 9 10 ...
Page 111: ...Electrical installation 111 2 360 grounding detail a b b 1 5 a 11 b a PE 10 7 5 6 8 ...
Page 117: ...Electrical installation 117 PE 11 8 4 9 11 ...
Page 134: ...134 Control units of the drive ...
Page 140: ...140 Start up ...
Page 142: ...142 Fault tracing ...
Page 154: ...154 Maintenance 4 5 6 7 8 6 10 10 ...
Page 162: ...162 Maintenance 5 6 3 4 7 ...
Page 163: ...Maintenance 163 6 8 7 11 10 9 ...
Page 167: ...Maintenance 167 3 4b 4a 4b 8 ...
Page 185: ...Technical data 185 Declaration of Conformity ...
Page 186: ...186 Technical data ...
Page 196: ...196 Dimensions Dimension drawing examples Frame 1 R8i 1 R8i ...
Page 197: ...Dimensions 197 Frame 1 R8i 1 R8i top cable entry exit H351 H353 ...
Page 198: ...198 Dimensions Frame 1 R8i 1 R8i with brake choppers and resistors D150 D151 ...
Page 199: ...Dimensions 199 Frame 1 R8i 1 R8i with sine output filter E206 ...
Page 200: ...200 Dimensions Frame 2 R8i 2 R8i eg ACS880 37 1110A 3 IP22 ...
Page 201: ...Dimensions 201 Frame 2 R8i 2 R8i eg ACS880 37 1210A 3 IP54 ...
Page 204: ...204 Dimensions Frame 2 R8i 2 R8i with main breaker F255 and top entry top exit H351 H353 1 2 ...
Page 205: ...Dimensions 205 Frame 2 R8i 2 R8i with main breaker F255 and top entry top exit H351 H353 2 2 ...
Page 206: ...206 Dimensions Frame 3 R8i 3 R8i 1 2 ...
Page 207: ...Dimensions 207 Frame 3 R8i 3 R8i 2 2 ...
Page 208: ...208 Dimensions Frame 3 R8i 3 R8i with common motor terminal cubicle H359 1 2 ...
Page 209: ...Dimensions 209 Frame 3 R8i 3 R8i with common motor terminal cubicle H359 2 2 ...
Page 217: ...Dimensions 217 Sine filter E206 cubicle 1000 mm top cable exit ...
Page 221: ...Dimensions 221 Cubicle width 400 mm top cable exit Cubicle width 600 mm bottom cable exit ...
Page 222: ...222 Dimensions Cubicle width 600 mm top cable exit ...
Page 234: ...234 The Safe torque off function ...
Page 244: ...www abb com drives www abb com drivespartners 3AXD50000020437 Rev A EN 2015 02 06 Contact us ...