Action
Safety
WARNING!
Obey the safety instructions during the start-up procedure. See chapter
Checks/Settings with no voltage connected
Ensure that the disconnector of the supply transformer is locked to the off (0) position, ie. no voltage
is, and cannot be connected to the drive inadvertently.
Check that the switch fuse (frame R8) (Q1) or main switch-disconnector (frame R11) (Q1) is switched
off.
Check the mechanical and electrical installation of the drive. See
.
Check the settings of breakers/switches in the auxiliary circuits. See the circuit diagrams delivered with
the drive.
Check the tap settings of transformers T21 (standard) and T101, T111 (if present). See
voltage range of auxiliary voltage transformers (page 109)
Disconnect any unfinished or uninspected auxiliary voltage (115/230 V AC) cables that lead from the
terminal blocks to the outside of the equipment.
Check that both channels of the Safe torque off circuit connected to the STO inputs of drive control
unit are closed. Refer to the wiring diagrams delivered with the drive.
If the Safe torque off functionality is used, check that the STO OUT output on the inverter control unit
is chained to the STO inputs of all inverter modules.
If the Safe torque off functionality is not used, check that the STO input on all inverter modules is correctly
wired to +24 V and ground.
For drives with ground fault monitoring for IT (ungrounded) systems (Q954): Adjust the settings
of the ground fault monitor to suit the installation. See the circuit diagrams of the delivery and
IRDH275B
Ground Fault Monitor Operating Manual
by Bender (code: TGH1386en).
For drives with Pt100 relays ((n)L506):
• Check the connections against the circuit diagrams of the delivery.
• Set the alarm and trip levels of the Pt100 relays.
Set the alarm and trip levels of the Pt100 relay as low as possible based on the operating temperature
and test results of the machine. The trip level can be set, for example, 10 °C higher than what the
temperature of the machine is at maximal load in the maximum environmental temperature.
We recommend to set the operating temperatures of the relay, typically for example, as follows:
• 120…140 °C when only tripping is in use
• alarm 120…140 °C and trip 130…150 °C when both alarm and tripping are used.
Powering up the auxiliary circuit of the drive
Make sure that it is safe to connect voltage. Ensure that
• nobody is working on the drive or circuits that have been wired from outside into the drive cabinet
• the cover of the motor terminal box is in place.
Drives with a voltmeter (G334): Make sure that the circuit breaker of the measuring circuit (F5)
is closed.
Close the circuit breakers and/or fuse disconnectors supplying the auxiliary voltage circuits.
Close the cabinet doors.
Close the main breaker of the supply transformer.
Close the switch fuse (frame R8) (Q1) or main switch-disconnector (frame R11) (Q1). This will power
up the main circuit of the drive as well as the auxiliary voltage circuit.
Note:
Do not use excessive force. The switch fuse (frame R8) or main switch-disconnector (frame R11)
can only be closed when the main input terminals (L1, L2, L3) are powered.
148 Start-up
Summary of Contents for ACS880-37
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 37 drives 45 400 kW 60 450 hp Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 83: ...Mechanical installation 83 10 ...
Page 84: ...84 ...
Page 126: ... B055 a X504 126 Electrical installation ...
Page 144: ...144 ...
Page 150: ...150 ...
Page 152: ...152 ...
Page 160: ... 160 Maintenance ...
Page 196: ... 196 Maintenance ...
Page 232: ...R8 IP22 UL Type 1 and option B054 IP42 UL Type 1 Filtered 232 Dimension drawings ...
Page 233: ...R8 IP54 UL Type 12 option B055 option C129 Dimension drawings 233 ...
Page 235: ...R8 IP22 UL Type 1 and IP42 UL Type 1 Filtered option B054 option E206 Dimension drawings 235 ...
Page 236: ...R8 IP22 UL Type 1 option E202 236 Dimension drawings ...
Page 237: ...R11 IP22 UL Type 1 and IP42 UL Type 1 Filtered option B054 Dimension drawings 237 ...
Page 238: ...R11 IP54 UL Type 12 option B055 238 Dimension drawings ...
Page 240: ...R11 IP54 UL Type 12 option B055 option C128 240 Dimension drawings ...
Page 241: ...R11 IP54 UL Type 12 option B055 option C129 Dimension drawings 241 ...
Page 242: ...R11 IP54 UL Type 12 option B055 options C129 H350 H352 242 Dimension drawings ...
Page 243: ...R11 IP22 UL Type 1 and IP42 UL Type 1 Filtered option B054 option D150 Dimension drawings 243 ...
Page 245: ...R11 IP22 UL Type 1 and IP42 UL Type 1 Filtered option B054 option E206 Dimension drawings 245 ...
Page 246: ...R11 IP22 UL Type 1 option E202 246 Dimension drawings ...
Page 267: ... Declaration of conformity The Safe torque off function 267 ...
Page 268: ...268 The Safe torque off function ...
Page 280: ...280 ...