Typical cable sizes
The table below gives copper and aluminum cable types with concentric copper shield for
nominal current. For drawings of the terminals, see chapter
UL
2)
IEC
1)
Frame
size
Drive type
ACS880-37-…
Cu cable size
Al cable size
Cu cable size
AWG/kcmil
mm
2
mm
2
U
N
= 400 V
1
3×70
3×50
R8
0105A-3
2/0
3×120
3×95
R8
0145A-3
3/0
3×150
3×120
R8
0169A-3
250 MCM
3×240
3×150
R8
0206A-3
2 × 3/0
2 × (3×120)
2 × (3×95)
R11
0293A-3
2 × 4/0
2 × (3×185)
2 × (3×120)
R11
0363A-3
2 × 250
3 × (3×120)
2 × (3×150)
R11
0442A-3
2×500 MCM or 3×250 MCM
3 × (3×150)
3 × (3×95)
R11
0505A-3
2×600 MCM or 3×300 MCM
3 × (3×185)
3 × (3×120)
R11
0585A-3
2×700 MCM or 3×350 MCM
3 × (3×240)
3 × (3×150)
R11
0650A-3
U
N
= 500 V
1
3×70
3×50
R8
0101A-5
2/0
3×95
3×95
R8
0124A-5
3/0
3×150
3×120
R8
0156A-5
250 MCM
3×185
3×150
R8
0180A-5
2 × 2/0
2 × (3×95)
2 × (3×70)
R11
0260A-5
2 × 250 MCM
2 × (3×185)
2 × (3×120)
R11
0302A-5
2 × 250 MCM
2 × (3×185)
2 × (3×120)
R11
0361A-5
2 × 250 MCM
2 × (3×240)
2 × (3×150)
R11
0414A-5
2×400 MCM or 3×4/0
3 × (3×120)
2 × (3×185)
R11
0460A-5
2×500 MCM or 3×250 MCM
3 × (3×150)
3 × (3×95)
R11
0503A-5
U
N
= 690 V
4/0
2 × (3×70)
3×120
R11
0174A-7
300 MCM
2 × (3×95)
3×185
R11
0210A-7
400 MCM
2 × (3×120)
3×240
R11
0271A-7
2 × 250 MCM or 3×2/0
2 × (3×150)
2 × (3×95)
R11
0330A-7
2 × 300 MCM or 3×3/0
2 × (3×150)
2 × (3×120)
R11
0370A-7
3×120) 2 × 350 MCM or 3×4/0
3 × (3×120)
2 × (3×185)
R11
0430A-7
The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays
one on top of the other, ambient temperature 30 °C, PVC insulation, surface temperature 70 °C (EN
60204-1 and IEC 60364-5-52/2001). For other conditions, size the cables according to local safety regu-
lations, appropriate input voltage and the load current of the drive.
1)
The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or
earth (directly buried). For other conditions, size the cables according to local safety regulations, appro-
priate input voltage and the load current of the drive.
2)
218 Technical data
Summary of Contents for ACS880-37
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 37 drives 45 400 kW 60 450 hp Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 83: ...Mechanical installation 83 10 ...
Page 84: ...84 ...
Page 126: ... B055 a X504 126 Electrical installation ...
Page 144: ...144 ...
Page 150: ...150 ...
Page 152: ...152 ...
Page 160: ... 160 Maintenance ...
Page 196: ... 196 Maintenance ...
Page 232: ...R8 IP22 UL Type 1 and option B054 IP42 UL Type 1 Filtered 232 Dimension drawings ...
Page 233: ...R8 IP54 UL Type 12 option B055 option C129 Dimension drawings 233 ...
Page 235: ...R8 IP22 UL Type 1 and IP42 UL Type 1 Filtered option B054 option E206 Dimension drawings 235 ...
Page 236: ...R8 IP22 UL Type 1 option E202 236 Dimension drawings ...
Page 237: ...R11 IP22 UL Type 1 and IP42 UL Type 1 Filtered option B054 Dimension drawings 237 ...
Page 238: ...R11 IP54 UL Type 12 option B055 238 Dimension drawings ...
Page 240: ...R11 IP54 UL Type 12 option B055 option C128 240 Dimension drawings ...
Page 241: ...R11 IP54 UL Type 12 option B055 option C129 Dimension drawings 241 ...
Page 242: ...R11 IP54 UL Type 12 option B055 options C129 H350 H352 242 Dimension drawings ...
Page 243: ...R11 IP22 UL Type 1 and IP42 UL Type 1 Filtered option B054 option D150 Dimension drawings 243 ...
Page 245: ...R11 IP22 UL Type 1 and IP42 UL Type 1 Filtered option B054 option E206 Dimension drawings 245 ...
Page 246: ...R11 IP22 UL Type 1 option E202 246 Dimension drawings ...
Page 267: ... Declaration of conformity The Safe torque off function 267 ...
Page 268: ...268 The Safe torque off function ...
Page 280: ...280 ...