Compliance with EN 61800-3:2004 + A1:2012
■
Definitions
EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic
equipment to operate without problems within an electromagnetic environment. Likewise,
the equipment must not disturb or interfere with any other product or system within its locality.
First environment
includes establishments connected to a low-voltage network which supplies
buildings used for domestic purposes.
Second environment
includes establishments connected to a network not supplying domestic
premises.
Drive of category C1
: drive of rated voltage less than 1000 V and intended for use in the
first environment.
Drive of category C2
: drive of rated voltage less than 1000 V and intended to be installed
and started up only by a professional when used in the first environment.
Note:
A professional
is a person or organization having necessary skills in installing and/or starting up power
drive systems, including their EMC aspects.
Drive of category C3
: drive of rated voltage less than 1000 V and intended for use in the
second environment and not intended for use in the first environment.
Drive of category C4
: drive of rated voltage equal to or above 1000 V, or rated current equal
to or above 400 A, or intended for use in complex systems in the second environment.
■
Category C2
The drive complies with the standard with the following provisions:
1.
The drive is equipped with EMC filter E202.
2.
The motor and control cables are selected as specified in the hardware manual.
3.
The drive is installed according to the instructions given in the hardware manual.
4.
Maximum motor cable length is 100 meters (328 ft).
WARNING!
The drive may cause radio interference if used in a residential or domestic
environment. The user is required to take measures to prevent interference, in
addition to the requirements for CE compliance listed above, if necessary.
Note:
Do not install a drive equipped with EMC E202/ARFI-10 on IT
(ungrounded) systems. The supply network becomes connected to ground potential
through the EMC filter capacitors which may cause danger or damage to the unit.
Note:
Do not install a drive equipped with EMC E202 on IT (ungrounded) systems.
The supply network becomes connected to ground potential through the EMC filter capacitors
which may cause danger or damage the unit.
■
Category C3
The drive complies with the standard with the following provisions:
1.
Frame R8: The drive is equipped with EMC filter E200 or +E201.
2.
The motor and control cables are selected as specified in the hardware manual.
3.
The drive is installed according to the instructions given in the hardware manual.
4.
Maximum motor cable length is 100 meters (328 ft).
Technical data 227
Summary of Contents for ACS880-37
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 37 drives 45 400 kW 60 450 hp Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 83: ...Mechanical installation 83 10 ...
Page 84: ...84 ...
Page 126: ... B055 a X504 126 Electrical installation ...
Page 144: ...144 ...
Page 150: ...150 ...
Page 152: ...152 ...
Page 160: ... 160 Maintenance ...
Page 196: ... 196 Maintenance ...
Page 232: ...R8 IP22 UL Type 1 and option B054 IP42 UL Type 1 Filtered 232 Dimension drawings ...
Page 233: ...R8 IP54 UL Type 12 option B055 option C129 Dimension drawings 233 ...
Page 235: ...R8 IP22 UL Type 1 and IP42 UL Type 1 Filtered option B054 option E206 Dimension drawings 235 ...
Page 236: ...R8 IP22 UL Type 1 option E202 236 Dimension drawings ...
Page 237: ...R11 IP22 UL Type 1 and IP42 UL Type 1 Filtered option B054 Dimension drawings 237 ...
Page 238: ...R11 IP54 UL Type 12 option B055 238 Dimension drawings ...
Page 240: ...R11 IP54 UL Type 12 option B055 option C128 240 Dimension drawings ...
Page 241: ...R11 IP54 UL Type 12 option B055 option C129 Dimension drawings 241 ...
Page 242: ...R11 IP54 UL Type 12 option B055 options C129 H350 H352 242 Dimension drawings ...
Page 243: ...R11 IP22 UL Type 1 and IP42 UL Type 1 Filtered option B054 option D150 Dimension drawings 243 ...
Page 245: ...R11 IP22 UL Type 1 and IP42 UL Type 1 Filtered option B054 option E206 Dimension drawings 245 ...
Page 246: ...R11 IP22 UL Type 1 option E202 246 Dimension drawings ...
Page 267: ... Declaration of conformity The Safe torque off function 267 ...
Page 268: ...268 The Safe torque off function ...
Page 280: ...280 ...