The wire size accepted by all screw terminals (for both stranded and solid wire) is 0.5 …
2.5 mm
2
(24…12 AWG). The torque is 0.5 N·m (5 lbf·in).
Drive-to-drive link
XD2D
Drive-to-drive link
1)
B
1
A
2
BGND
3
Shield
4
RS485 connection
X485
Not in use
B
5
A
6
BGND
7
Shield
8
Relay outputs
XRO1…XRO3
Ready
250 V AC / 30 V DC
2 A
NC
11
COM
12
NO
13
Running
250 V AC / 30 V DC
2 A
NC
21
COM
22
NO
23
Faulted(-1)
250 V AC / 30 V DC
2 A
NC
31
COM
32
NO
33
Safe torque off
XSTO, XSTO OUT
Safe torque off input. Both circuits must be closed for the
drive to start.
2)
OUT
1
SGND
2
IN1
3
IN2
4
Safe torque off output to inverter modules
2)
IN1
5
SGND
6
IN2
7
SGND
8
Digital inputs
XDI
Stop (0) / Start (1)
DI1
1
Forward (0) / Reverse (1)
DI2
2
Reset
DI3
3
Acceleration & deceleration select
3)
DI4
4
Constant speed 1 select (1 = on)
4)
DI5
5
By default not in use.
DI6
6
Run enable
5)
DIIL
7
Digital input/outputs
XDIO
Output: Ready
DIO1
1
Output: Running
DIO2
2
Digital input/output ground
DIOGND
3
Digital input/output ground
DIOGND
4
Auxiliary voltage output
XD24
+24 V DC 200 mA
6)
+24VD
5
Digital input ground
DICOM
6
+24 V DC 200 mA
6)
+24VD
7
Digital input/output ground
DIOGND
8
Ground selection switch
7)
DICOM=DIOGND
Analog inputs, reference voltage output
AI
10 V DC,
R
L
1…10 kohm
+VREF
1
-10 V DC,
R
L
1…10 kohm
-VREF
2
Ground
AGND
3
Speed reference
0(2)…10 V,
R
in
> 200 kohm
8)
AI1+
4
AI1-
5
By default not in use.
0(4)…20 mA,
R
in
= 100 ohm
9)
AI2+
6
AI2-
7
Analog outputs
AO
Motor speed rpm
0…20 mA,
R
L
< 500 ohm
AO1
1
AGND
2
Motor current
0…20 mA,
R
L
< 500 ohm
AO2
3
AGND
4
External power input
XPOW
24 V DC, 2.05 A
Two supplies can be connected for redundancy.
+24VI
1
GND
2
+24VI
3
GND
4
Safety functions module connection
X12
Control panel connection
X13
Memory unit connection
X205
Fault
To inverter modules
Notes:
1)
See section
.
2)
See chapter
The Safe torque off function (page 183)
.
3)
0 = Acceleration/deceleration ramps defined by parameters 23.12/23.13 in use. 1 =
Acceleration/deceleration ramps defined by parameters 23.14/23.15 in use.
104 Control units of the drive
Summary of Contents for ACS880-37LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 37LC drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 78: ...78 ...
Page 116: ...116 ...
Page 134: ...5 Set the real time clock 134 Maintenance ...
Page 144: ...144 ...
Page 167: ... Dimension drawing examples ACS880 37LC 0390A 7 with main contactor Dimensions 167 ...
Page 169: ...ACS880 37LC 1270A 7 with common motor terminal cubicle Dimensions 169 ...
Page 170: ...ACS880 37LC 1940A 7 with common motor terminal cubicle 170 Dimensions ...
Page 172: ...Location and size of input terminals Contact ABB for details 172 Dimensions ...
Page 174: ...Inverter module cubicle with two R8i modules bottom cable exit 174 Dimensions ...
Page 175: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 175 ...
Page 176: ...Brake chopper cubicle D150 176 Dimensions ...
Page 178: ...Cubicle width 300 mm top cable exit 178 Dimensions ...
Page 179: ...Cubicle width 400 mm bottom cable exit Dimensions 179 ...
Page 180: ...Cubicle width 400 mm top cable exit 180 Dimensions ...
Page 181: ...Cubicle width 600 mm bottom cable exit Dimensions 181 ...
Page 182: ...Cubicle width 600 mm top cable exit 182 Dimensions ...
Page 198: ...198 ...
Page 200: ...200 ...