Parameters 137
Defines the activation delay for digital input/output DIO2
(when used as a digital output or digital input).
0.0 s
t
On
t
Off
*Electrical status of DIO (in input mode) or status of selected source (in output mode). Indicated by
.
0.0…3000.0 s
Activation delay for DIO2.
10 = 1 s
Defines the deactivation delay for digital input/output DIO2
(when used as a digital output or digital input). See
parameter
.
0.0 s
0.0…3000.0 s
Deactivation delay for DIO2.
10 = 1 s
Displays the value of frequency input 1 (via DIO1 when it is
used as a frequency input) before scaling. See parameter
This parameter is read-only.
-
0…16000 Hz
Unscaled value of frequency input 1.
1 = 1 Hz
Displays the value of frequency input 1 (via DIO1 when it is
used as a frequency input) after scaling. See parameter
This parameter is read-only.
-
-32768.000
…32767.000
Scaled value of frequency input 1.
1 = 1
No.
Name/Value
Description
Def/
FbEq16
1
0
1
0
t
On
t
Off
t
On
t
Off
*DIO status
Time
**Delayed DIO
status
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...