186 Parameters
Selects the source for the start enable signal.
1 = Start enable.
With the signal switched off, any drive start command is
inhibited. (Switching the signal off while the drive is
running will not stop the drive.)
Notes
:
• If a level-triggered start command is on when the start
enable signal switches on, the drive will start. (An edge-
triggered start signal must be cycled for the drive to
start.) See parameters
and
• The warning that indicates a missing signal can be
suppressed using parameter
.
See also parameter
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0). 10
DIO2
Digital input/output DIO2 (
, bit 1). 11
DIIL
DIIL input (
, bit 15).
30
Source selection (see
on
page
-
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...