Fieldbus control through the embedded fieldbus interface (EFB) 439
Setting up the embedded fieldbus interface
Set the drive up for the embedded fieldbus communication with the parameters
shown in the table below. The
Setting for fieldbus control
column gives either the
value to use or the default value. The
Function/Information column
gives a
description of the parameter.
Parameter
Setting for
fieldbus control
Function/Information
COMMUNICATION INITIALIZATION
Initializes embedded fieldbus communication.
Drive-to-drive link operation is automatically
disabled.
EMBEDDED MODBUS CONFIGURATION
1 (default)
Node address. There must be no two nodes
with the same node address online.
(default) Defines the communication speed of the link.
Use the same setting as in the master station.
(default) Selects the parity and stop bit setting. Use the
same setting as in the master station.
(default)
Defines the action taken when a
communication loss is detected.
(default)
Enables/disables communication loss
monitoring and defines the means for
resetting the counter of the communication
loss delay.
3.0 s (default)
Defines the timeout limit for the
communication monitoring.
0 ms (default)
Defines a response delay for the drive.
(default),
Selects the control profile used by the drive.
See section
Basics of the embedded fieldbus
(page
).
…
…
,
,
,
Selects the reference and actual value types.
With the
setting, the type
is selected automatically according to the
currently active drive control mode.
EFB status word
transparent
source
Defines the source of status word when
Defines the source of actual value 1 when
Defines the source of actual value 2 when
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...