Parameters 157
(Visible when
Selects the unit for readings and settings related to analog
input AI1.
Note: This setting must match the corresponding hardware
setting on the I/O extension module (see the manual of the
I/O extension module). The hardware setting is shown by
parameter
. I/O module reboot
either by cycling the power or through parameter
is required to validate any changes in
the hardware settings.
V
Volts.
2
mA
Milliamperes.
10
(Visible when
Status of relay outputs on the I/O extension module.
Example: 00000001b = RO1 is energized, RO2 is de-
energized.
-
0000b…1111b
Status of relay outputs.
1 = 1
(Visible when
Selects a hardware filtering time for AI1.
See also parameter
No filtering
No filtering.
0
125 us
125 microseconds.
1
250 us
250 microseconds.
2
500 us
500 microseconds.
3
1 ms
1 millisecond.
4
2 ms
2 milliseconds.
5
4 ms
4 milliseconds.
6
7.9375 ms
7.9375 milliseconds.
7
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...