Parameters 237
Defines the minimum allowed frequency.
WARNING!
This value must not be higher than
.
WARNING!
This limit is effective in frequency
control mode only.
-50.00 Hz;
-60.00 Hz
(
-500.00…500.00 Hz
Minimum frequency.
See par.
Defines the maximum allowed frequency.
WARNING!
This value must not be lower than
WARNING!
This limit is effective in frequency
control mode only.
50.00 Hz;
60.00 Hz
(
-500.00…500.00 Hz
Maximum frequency.
See par.
A temporary motor current limit specifically for starting can
be defined by this parameter and
.
When this parameter is set to
, the drive observes
the start current limit defined by
. The limit is in force for 2 seconds after initial
magnetization (of an asynchronous induction motor) or
autophasing (of a permanent magnet motor), but not more
often than once in every 7 seconds. Otherwise, the limit
defined by
is in force.
Note:
The availability of a start current higher than the
general limit depends on drive hardware.
Disable
Start current limit disabled.
0
Enable
Start current limit enabled.
1
Defines the maximum start current when enabled by
parameter
.
-
0.00...30000.00 A
Maximum motor start current.
1 = 1 A
Defines the maximum allowed motor current.
0.00 A
0.00…30000.00 A
Maximum motor current.
1 = 1 A
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...