416 Fault tracing
A7E2
Encoder 2
Encoder 2 error.
Check that the parameter settings in
groups
are
correct.
Note:
New settings will only take effect
drive control unit is powered up the
next time.
Check the auxiliary code. See
appropriate actions for each code
below.
Aux code: 1030
Overspeed
Contact your local ABB representative.
Aux code: 1031
Pulse overfrequency
Aux code: 1032
Cable fault
Check the wiring of the encoder.
See also parameters
.
Aux code: 1033
Resolver ID run fault
Contact your local ABB representative.
Aux code: 1034
Encoder fault
Refer to encoder documentation.
Aux code: 1035
Encoder warning
Aux code: 1036
Unsupported cable fault
detection mode.
.
Aux code: 1037
Resolver SW version
Contact your local ABB representative.
Aux code: 1038
Resolver speed scale
A7EE
Panel loss
Programmable warning:
Control panel or PC tool
selected as active control
location for drive has
ceased communicating.
Check PC tool or control panel
connection.
Check control panel connector.
Disconnect and reconnect the control
panel.
A880
Motor bearing
Programmable warnings:
Warning generated by an
on-time timer or a value
counter.
Check the auxiliary code. Check the
source of the warning corresponding
to the code:
0:
A881
Output relay
Warning generated by an
edge counter.
Programmable warnings:
Check the auxiliary code. Check the
source of the warning corresponding
to the code:
2:
A882
Motor starts
A883
Power ups
A884
Main contactor
A885
DC charge
A886
On-time 1
(Editable message text)
Programmable warning:
Warning generated by
on-time timer 1.
Check the source of the warning
(parameter
A887
On-time 2
(Editable message text)
Programmable warning:
Warning generated by
on-time timer 2.
Check the source of the warning
(parameter
Code
(hex)
Warning
Cause
What to do
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...