Fault tracing 431
EnDat or SSI encoder is
used in continuous mode as
encoder 2.
(I.e.
90.02
Encoder 2 sel
=
FEN-11 ABS
and 91.02 ABS ENC INTERF
= EnDat [or 91.02 ABS ENC
INTERF = SSI]
and 91.30 ENDAT MODE =
CONTINUOUS [or 91.25 SSI
MODE = CONTINUOUS].)
If possible, use single position
transfer instead of continuous
position transfer (i.e. if encoder has
incremental sin/cos signals):
- Change parameter 91.25 SSI
MODE / 91.30 ENDAT MODE to
value INITIAL POS.
Otherwise use Endat/SSI encoder
as encoder 1:
- Change parameter
90.01
Encoder 1 sel
to value
FEN-11
ABS
and parameter
90.02
Encoder
2 sel
to value
None
.
Note:
The new setting will only
take effect after parameter
is used
or after the JCU Control Unit is
powered up the next time.
73A0
Speed feedback
configuration
Speed feedback
configuration incorrect.
Check the feedback source
selection parameters in group
. In case the
source is an encoder interface,
check parameter settings in groups
and
.
Check the event log for an auxiliary
code. See appropriate actions for
each code below.
Aux code: 1000
Interface module location
settings in conflict.
Check the module location settings
(
and
Aux code: 1001
Detected type of interface
module 1 does not match
setting.
Check setting of
against
.
Check setting of
Aux code: 1002
Detected type of interface
module 2 does not match
setting.
Check setting of
against
.
Check setting of
Aux code: 1003
Interface module 1 type does
not match encoder type.
Check settings of
and
.
Aux code: 1004
Interface module 2 type does
not match encoder type.
Check settings of
and
.
Aux code: 1005
Speed feedback
configuration has changed.
Use parameter
) to validate any
changes in the settings.
73A1
Load feedback
No load feedback received.
Check the auxiliary code. See
appropriate actions for each code
below.
Code
(hex)
Fault
Cause
What to do
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...