488 Appendix: ESP with step-up transformer and sine filter
Current calculation
For ESP with sine filter and step-up transformer instead of using the motor rating
plate data, set parameter
supply voltage of the drive (example: 690 V). Also set the parameter
to
Where U
1
and U
2
are the primary and secondary voltages of the step-up transformer
respectively.
Primary and secondary voltage calculation
Required data:
Motor:
Cable:
If the cable characteristics are not known, typical values can be used:
Motor data:
Nominal impedance,
Resistive component,
Reactive component,
Cable reactance at frequency
f,
U
2
U
1
------
I
n
⋅
U
n
I
n
ϕ
n
( )
f
n
,
cos
,
,
R
c
L
c
length
,
,
R
c
0.27
Ω
km
-------
=
L
c
0.33
mH
km
---------
=
Z
m
U
n
I
n
3
⋅
----------------
=
R
m
Z
m
ϕ
n
( )
cos
⋅
=
X
m
Z
m
1
2
cos
ϕ
n
( )
–
⋅
=
X
c
2
π
fL
c
=