Motor overload protection
This section describes motor overload protection without using motor thermal
protection model, either with estimated or measured temperature. For protection
with the motor thermal protection model, see section
Motor overload protection is required and specified by multiple standards including
the US National Electric Code (NEC), UL 508C and the common UL\IEC 61800-5-1
standard in conjunction with IEC 60947-4-1. The standards allow for motor overload
protection without external temperature sensors.
The Motor overload protection fulfills standard IEC/EN 61800-5-1 ed. 2.1
requirements for thermal memory retention and speed sensitivity. The estimated
temperature is retained over power down. Speed dependency is set by parameters.
The protection feature allows the user to specify the class of operation in the same
manner as the overload relays are specified in standards IEC 60947-4-1 and NEMA
ICS 2.
Motor overload protection requires that you specify a motor current tripping level.
This is defined by a curve using parameters
and
. The tripping
level is the motor current at which the overload protection will ultimately trip if
the motor current remains at this level continuously.
The motor overload class (class of operation), parameter
, is given as the
time required for the overload relay to trip when operating at 7.2 times the tripping
level in the case of IEC 60947-4-1 and 6 times the tripping level in the case of NEMA
ICS 2. The standards also specify the time to trip for current levels between the
tripping level and the 6 times tripping level. The drive satisfies the IEC standard
and NEMA standard trip times.
Using class 20 satisfies the UL 508C requirements.
The motor overload algorithm monitors the squared ratio (motor current / tripping
level)
2
and accumulates this over time. This is sometimes referred to as I
2
t
protection. The accumulated value is shown in parameter
.
You can define with parameter
that when
reaches 88%, a motor overload
warning will be generated, and when it reaches 100%, the drive will trip on the
motor overload fault. The rate at which this internal value is increased depends
on the actual current, tripping level current and overload class selected.
Parameters
and
serve a dual purpose. They determine the load
curve for temperature estimate as well as specify the overload tripping level.
Settings and diagnostics
Parameters common to motor thermal protection and motor overload protection:
…
Program features 115
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...