Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
- / uint16
(Visible when
=
Shows the position of the hardware current/voltage
selector on the I/O extension module.
Note: The setting of the current/voltage selector must
match the unit selection made in parameter
. I/O module reboot either by cycling the
power or through parameter
is required to validate any changes in the hardware
settings.
AI3 HW switch
position
14.59
10
Milliamperes.
mA
2
Volts.
V
mA / uint16
(Visible when
=
Selects the unit for readings and settings related to
analog input AI3.
Note: This setting must match the corresponding
hardware setting on the I/O extension module (see the
manual of the I/O extension module). The hardware
setting is shown by parameter
. I/O module reboot either by cycling the power
or through parameter
is
required to validate any changes in the hardware
settings.
AI3 unit selection
14.60
10
Milliamperes.
mA
2
Volts.
V
1 ms / uint16
(Visible when
=
Selects a hardware filtering time for AI3.
See also parameter
.
AI3 filter gain
14.61
0
No filtering.
No filtering
1
125 microseconds.
125 us
2
250 microseconds.
250 us
3
500 microseconds.
500 us
4
1 millisecond.
1 ms
5
2 milliseconds.
2 ms
6
4 milliseconds.
4 ms
7
7.9375 milliseconds.
7.9375 ms
Parameters 217
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...