Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Selection of local and external control location sources
and operating modes.
Operation mode
19
See also section
.
- / uint16
Displays the operating mode currently used.
See parameters
…
Actual operation
mode
19.1
This parameter is read-only.
1
None.
Zero
2
Speed control (in DTC motor control mode).
Speed
3
Torque control (in DTC motor control mode).
Torque
4
The torque selector is comparing the output of the
speed controller (
25.1 Torque reference speed control
Min
and torque reference (
) and
the smaller of the two is used.
5
The torque selector is comparing the output of the
speed controller (
25.1 Torque reference speed control
Max
and torque reference (
) and
the greater of the two is used.
6
The speed controller output is added to the torque
reference.
Add
7
DC voltage control.
16
Position control.
17
Synchron control.
18
Homing control.
19
Profile velocity control.
EXT1 / uint32
Selects the source for external control location
EXT1/EXT2 selection.
Ext1/Ext2 selection
19.11
0 = EXT1
1 = EXT2
0
EXT1 (permanently selected).
EXT1
1
EXT2 (permanently selected).
EXT2
2
Control word bit 11 received through fieldbus interface
A.
FBA A MCW bit 11
3
Digital input DI1 (
, bit 0).
DI1
4
Digital input DI2 (
, bit 1).
DI2
5
Digital input DI3 (
, bit 2).
DI3
6
Digital input DI4 (
, bit 3).
DI4
7
Digital input DI5 (
, bit 4).
DI5
8
Digital input DI6 (
, bit 5).
DI6
11
Digital input/output DIO1 (
, bit
0).
DIO1
12
Digital input/output DIO2 (
, bit
1).
DIO2
238 Parameters
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...