Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Enables/disables (or selects a source that
enables/disables) speed error window control,
sometimes also referred to as deadband control or
strip break protection. It forms a speed supervision
function for a torque-controlled drive, preventing the
motor from running away if the material that is being
held under tension breaks.
Note: Speed error window control is only effective when
the
operating mode is active (see parameters
and
), or when the drive is a speed-controlled
follower (see page
).
In normal operation, window control keeps the speed
controller input at zero so the drive stays in torque
control.
If the motor load is lost, then the motor speed will rise
as the torque controller tries to maintain torque. The
speed error (speed reference - actual speed) will
increase until it exits the speed error window. When
this is detected, the exceeding part of the error value
is connected to the speed controller. The speed
controller produces a reference term relative to the
input and gain (
) which
the torque selector adds to the torque reference. The
result is used as the internal torque reference for the
drive.
The activation of speed error window control is
indicated by bit 3 of
6.19 Speed control status word
The window boundaries are defined by
and
as follows:
282 Parameters
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...