Description
Term
Connection
XRO1, XRO2, XRO3 Relay outputs
Ready run
NC
1
2
3
1
2
3
1
2
3
+24VD
DIOGND
NC
COM
NO
NC
COM
NO
NC
COM
NO
Fault
250 V AC / 30 V DC
2 A
COM
NO
Running
250 V AC / 30 V DC
2 A
NC
COM
NO
Fault (-1)
250 V AC / 30 V DC
2 A
NC
COM
NO
XD24 Digital interlock
Run enable
DIIL
DIIL
1
+24VD
DICOM
+24VD
DIOGND
2
3
4
5
+24 V DC 200 mA
+24VD
Digital input ground
DICOM
+24 V DC 200 mA
+24VD
Digital input/output ground
DIOGND
XDIO Digital input/outputs
:
DIO1
1
DIO1
2
DIO2
:
DIO2
XDI Digital inputs
Stop (0) / Start (1)
DI1
1
DI1
DI2
DI3
DI4
DI5
DI6
2
3
4
5
6
+24VD
Forward (0) / Reverse (1)
DI2
Reset
DI3
Acc/Dec time set 1 (0) / set 2 (1)
DI4
Constant speed 1 (1 = On)
DI5
By default, not in use.
DI6
Safe torque off circuits must be closed for the drive
to start. See
Hardware manual of drive.
XSTO
Safety options connection
X12
Control panel connection
X13
Memory unit connection
X205
Default control connections 31