Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
150.00; 180.00 rpm
(95.20 b0) rpm /
real32
Stall speed limit in rpm. See parameter
Stall speed limit
31.26
- / -
Stall speed limit. For scaling, see parameter
.
0.00 ... 10000.00
rpm
15.00; 18.00 Hz (95.20
b0) Hz / real32
Stall frequency limit. See parameter
.
Note: Setting the limit below 10 Hz is not
recommended.
Stall frequency limit
31.27
- / -
Stall frequency limit. For scaling, see parameter
.
0.00 ... 500.00 Hz
20 s / real32
Stall time. See parameter
Stall time
31.28
1 = 1 s / 1 = 1 s
Stall time.
0...3600 s
500.00 rpm / real32
Defines, together with
and
, the maximum allowed speed of the
motor (overspeed protection). If
or the estimated speed exceeds the speed limit
defined by parameter
or
by more than the
value of this parameter, the drive trips on the
.
Example: If the maximum speed is 1420 rpm and speed
trip margin is 300 rpm, the drive trips at 1720 rpm.
Speed (90.01)
Time
Overspeed trip level
(
31.30)
(
30.12)
(
30.11 )
(
31.30)
Overspeed trip level
0
Overspeed trip
margin
31.30
- / -
Overspeed trip margin. For scaling, see parameter
.
0.00 ... 10000.00
rpm
Parameters 323