Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
1000 = 1 units/s^2 /
1 = 1 units/s^2
Maximum acceleration for jogging.
0.000 ...
20000000.000
units/s^2
10.000 units/s^2 /
real32
Defines the maximum deceleration rate used during
jogging.
Jogging
deceleration
75.23
1000 = 1 units/s^2 /
1 = 1 units/s^2
Maximum deceleration for jogging.
0.000 ...
20000000.000
units/s^2
0.000 units/s^3 /
real32
Defines the maximum jerk value to be used during
jogging.
Note: 0.000 = unlimited.
Jogging jerk
75.24
1000 = 1 units/s^3 /
1 = 1 units/s^3
Maximum jerk for jogging.
0.000 ...
20000000.000
units/s^3
20.000 units/s^2 /
real32
Defines the deceleration rate for stopping.
This value must be higher than that in the active profile.
Otherwise this value is ignored and a warning (
) generated.
Stop deceleration
75.31
1000 = 1 units/s^2 /
1 = 1 units/s^2
Deceleration rate for stopping.
0.000 ...
20000000.000
units/s^2
0.000 units/s^3 /
real32
Defines the jerk value for stopping.
This value must be higher than that in the active profile.
Otherwise this value is ignored and a warning (
) generated.
Note: 0.000 = unlimited.
Stop jerk
75.32
1000 = 1 units/s^3 /
1 = 1 units/s^3
Deceleration rate for stopping.
0.000 ...
20000000.000
units/s^3
0.000 units / real32
Defines a preset position for several selections of
parameter
.
Preset position
75.35
1000 = 1 units / 1 = 1
units
Preset position.
-2000000.000 ...
2000000.000 units
Axis immediate /
int16
Selects the preset position mode.
See also
86.69 Position offset retention
for the action
taken at power-up.
Preset position
mode
75.36
0
Sets the actual axis position value to that of
Axis immediate
Parameters 451
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...