System overview
The drive can be connected to an external control system through a communication
link using either a fieldbus adapter or the embedded fieldbus interface.
The embedded fieldbus interface supports the Modbus RTU protocol. The drive
control program can handle 10 Modbus registers in a 10-millisecond time level.
For example, if the drive receives a request to read 20 registers, it will start its
response within 22 ms of receiving the request – 20 ms for processing the request
and 2 ms overhead for handling the bus. The actual response time depends on
other factors as well, such as the baud rate (a parameter setting in the drive).
The drive can be set to receive all of its control information through the fieldbus
interface, or the control can be distributed between the embedded fieldbus
interface and other available sources, for example, digital and analog inputs.
...
Fieldbus controller
Fieldbus
Process I/O (cyclic)
Service messages
(acyclic)
Control Word (CW)
Reference
Status Word (SW)
Actual values
Parameter R/W requests/responses
XD2D
XD2D
XD2D
ACS880
ACS880
ACS880
Termination
OFF
Termination
ON
Termination
OFF
Control unit
Control unit
Control unit
Data Flow
Connecting the fieldbus to the drive
Connect the fieldbus to terminal XD2D on the control unit of the drive. See the
appropriate
Hardware Manual for more information on the connection, chaining
and termination of the link.
Note: If the XD2D connector is reserved by the embedded fieldbus interface
(parameter
is set to
), the drive-to-drive link
functionality is automatically disabled.
606 Fieldbus control through the embedded fieldbus interface (EFB)
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...