Description
Setting for
ACS880 drives
Drive parameter
Acceleration time 1
53.03 FBA data out3
Deceleration time 1
23.13
53.05 FBA data out5
Validates the configuration parameter set-
tings.
1 =
Selects speed control as the control mode 1
for external control location EXT1.
2 =
Selects fieldbus adapter A as the source of
the start and stop commands for external
control location EXT1.
12 =
Selects a level-triggered start signal for ex-
ternal control location EXT1.
1 =
Selects fieldbus A reference 1 as the source
for speed reference 1.
4 = FB A ref1
1) Read-only or automatically detected/set
2) Example
The start sequence for the parameter example above is given below.
Control word
•
after power-on, fault or emergency stop:
•
476h (1142 decimal) –> NOT READY TO SWITCH ON
•
in normal operation:
•
477h (1143 decimal) –> READY TO SWITCH ON (stopped)
•
47Fh (1151 decimal) –> OPERATING (running)
Fieldbus control through a fieldbus adapter 639