Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
10 = 1 s / 10 = 1 s
Activation delay for RO1.
0.0 ... 3000.0 s
0.0 s / uint32
Defines the deactivation delay for relay output RO1.
See parameter
.
RO1 OFF delay
10.26
10 = 1 s / 10 = 1 s
Deactivation delay for RO1.
0.0 ... 3000.0 s
Running (95.20 b3) /
uint32
Selects a drive signal to be connected to relay output
RO2.
For the available selections, see parameter
RO2 source
10.27
0.0 (95.20 b3) s /
uint32
Defines the activation delay for relay output RO2.
Status of selected
source
RO status
t
On
t
Off
t
Off
t
On
1
0
0
1
Time
t
On
=
t
Off
=
RO2 ON delay
10.28
10 = 1 s / 10 = 1 s
Activation delay for RO2.
0.0 ... 3000.0 s
0.0 (95.20 b3) s /
uint32
Defines the deactivation delay for relay output RO2.
See parameter
.
RO2 OFF delay
10.29
10 = 1 s / 10 = 1 s
Deactivation delay for RO2.
0.0 ... 3000.0 s
Fault (-1) / uint32
Selects a drive signal to be connected to relay output
RO3.
For the available selections, see parameter
RO3 source
10.30
0.0 s / uint32
Defines the activation delay for relay output RO3.
Status of selected
source
RO status
Time
1
0
1
0
t
On
t
On
t
Off
t
Off
t
On
=
t
Off
=
RO3 ON delay
10.31
10 = 1 s / 10 = 1 s
Activation delay for RO3.
0.0 ... 3000.0 s
0.0 s / uint32
Defines the deactivation delay for relay output RO3.
See parameter
.
RO3 OFF delay
10.32
10 = 1 s / 10 = 1 s
Deactivation delay for RO3.
0.0 ... 3000.0 s
10.0 ms / uint32
Defines a filtering time for parameters
and
.
DI filter time
10.51
10 = 1 ms / 10 = 1 ms
Filtering time for
and
.
0.3 ... 100.0 ms
178 Parameters
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...