Selects the source of the motor pre-heat on/off
command.
See section
Note: The pre-heating function will not activate if
•
the Safe torque off function is active,
•
a fault is active,
•
less than one minute has elapsed after stopping,
or
•
PID sleep function is active.
Pre-heating is deactivated when the drive is started,
and overridden by pre-magnetization,
post-magnetization or continuous magnetization.
0 = Pre-heating inactive
1 = Pre-heating active
Pre-heating input
source
21.14
0
0. Pre-heating is always deactivated.
Inactive (false)
1
1. Pre-heating is always activated when the drive is
stopped (apart from conditions stated above).
Active (true)
2
Digital input DI1 (
, bit 0).
DI1
3
Digital input DI2 (
, bit 1).
DI2
4
Digital input DI3 (
, bit 2).
DI3
5
Digital input DI4 (
, bit 3).
DI4
6
Digital input DI5 (
, bit 4).
DI5
7
Digital input DI6 (
, bit 5).
DI6
8
Supervision 1 active (
, bit 0).
Supervision 1
9
Supervision 2 active (
, bit 1).
Supervision 2
10
Supervision 3 active (
, bit 2).
Supervision 3
See
Terms and abbreviations (page 130)
.
Other [bit]
60 s / real32
Defines the delay time for the pre-heating function.
Pre-heating time
delay
21.15
1 = 1 s / 1 = 1 s
Pre-heating time delay.
10...3000 s
0.0 % / real32
Defines the motor pre-heating current that is fed into
the motor when the source selected by
is on. The value is in percent
of the nominal motor current.
Pre-heating current
21.16
1 = 1 % / 10 = 1 %
Pre-heating current.
0.0 ... 30.0 %
Parameters 259
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...