Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
17
Pt1000 sensor connected to encoder interface 2. See
parameters
91.24 Module 2 temp sensor type
and
Note: Pt1000 sensor supports FEN-11 and FEN-31
encoder modules only.
Pt1000 encoder
module 2
130 ° / real32
Defines the fault limit for temperature monitoring
function 1.
When measured temperature 1 exceeds the limit, the
drive trips on fault
The unit is selected by parameter
Note: With °F, the range is -76…1832. With a PTC sensor,
the range is 0…5000 ohms.
Temperature 1 fault
limit
35.12
1 = 1 ° / 1 = 1 °
Fault limit for temperature monitoring function 1.
-60...1000 °
110 ° / real32
Defines the warning limit for temperature monitoring
function 1. When measured temperature 1 exceeds this
limit, a warning (
) is
generated.
The unit is selected by parameter
Note: With °F, the range is -76…1832. With a PTC sensor,
the range is 0…5000 ohms.
Temperature 1
warning limit
35.13
1 = 1 ° / 1 = 1 °
Warning limit for temperature monitoring function 1.
-60...1000 °
Not selected / uint32
Specifies the analog input when the setting of
requires measurement through
an analog input.
Note: If the input is located on an I/O extension module,
use the selection
Other to point to the AI actual value
in group 14, 15 or 16, eg.
Temperature 1 AI
source
35.14
0
None.
Not selected
1
Analog input AI1 on the control unit.
AI1 actual value
2
Analog input AI2 on the control unit.
AI2 actual value
See
Terms and abbreviations (page 130)
Other [value]
0 ° / real32
Defines the calibration of temperature 1.
Calibration can be used to fine-tune the motor
temperature measurement. Once the motor has cooled
down, measure its ambient temperature and set this
value accordingly.
This parameter affects only if Pt100 or Pt1000
measurement is using AI and AO of the control unit or
I/O extension modules.
Temperature 1
calibration
35.17
1 = 1 ° / 1 = 1 °
Calibration of temperature 1 in celsius.
-30...1000 °
344 Parameters
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...