Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
1 = Yes: Warnings from the module in slot 1 suppressed.
Disable slot 1
warning
b1
1 = Yes: Module installed in slot 2.
Module in slot 2
b2
1 = Yes: Warnings from the module in slot 2 suppressed.
Disable slot 2
warning
b3
1 = Yes: Module installed in slot 3.
Module in slot 3
b4
1 = Yes: Warnings from the module in slot 3 suppressed.
Disable slot 3
warning
b5
Reserved
b6…15
1 = 1
0000h…FFFFh
20 ° / real32
Defines the ambient temperature of the motor for the
motor thermal protection model. The unit (°C or °F) is
selected by parameter
The motor thermal protection model estimates the
motor temperature on the basis of parameters
…
. The motor temperature increases if it
operates in the region above the load curve, and
decreases if it operates in the region below the load
curve.
WARNING!
The model cannot protect the motor if the
motor does not cool properly because of dust,
dirt, etc.
Motor ambient
temperature
35.50
1 = 1 ° / 1 = 1 °
Ambient temperature.
-60...100 °
100 % / uint16
Defines the motor load curve together with parameters
and
. The load
curve is used by the motor thermal protection model
to estimate the motor temperature.
When the parameter is set to 100%, the maximum load
is taken as the value of parameter
(higher loads heat up the motor). The load curve
level should be adjusted if the ambient temperature
differs from the nominal value set in
I
= Motor current
I
N
= Nominal motor current
Drive output
frequency
I/I
N
(%)
150
100
50
35.52
35.53
35.51
Motor load curve
35.51
348 Parameters
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...