Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Motor model settings.
Motor control
97
4.500 kHz / real32
When parameter
is set to
, defines the switching frequency when it is not
otherwise being internally limited.
Switching frequency
reference
97.1
Note: This is an expert level parameter and should not
be adjusted without appropriate skill.
1000 = 1 kHz / 1000 =
1 kHz
Switching frequency reference.
0.000 ... 24.000 kHz
1.500 kHz / real32
When parameter
is set to
, defines a minimum switching frequency
Minimum switching
frequency
97.2
reference. The actual switching frequency will not fall
below this limit under any circumstances.
Note: This is an expert level parameter and should not
be adjusted without appropriate skill.
Note: The drive has internal switching frequency limits
that may override the value entered here.
1000 = 1 kHz / 1000 =
1 kHz
Minimum switching frequency.
0.000 ... 24.000 kHz
100 % / real32
Defines the slip gain which is used to improve the
estimated motor slip. 100% means full slip gain; 0%
Slip gain
97.3
means no slip gain. The default value is 100%. Other
values can be used if a static speed error is detected
despite having the setting at full slip gain.
Example (with nominal load and nominal slip of 40
rpm): A 1000 rpm constant speed reference is given to
the drive. Despite having full slip gain (= 100%), a
manual tachometer measurement from the motor axis
gives a speed value of 998 rpm. The static speed error
is 1000 rpm - 998 rpm = 2 rpm. To compensate the
error, the slip gain should be increased to 105%
(2 rpm / 40 rpm = 5%).
1 = 1 % / 100 = 1 %
Slip gain.
0...200 %
-2 % / real32
Defines the minimum allowed voltage reserve. When
the voltage reserve has decreased to the set value, the
drive enters the field weakening area.
Voltage reserve
97.4
Note: This is an expert level parameter and should not
be adjusted without appropriate skill.
If the intermediate circuit DC voltage
U
dc
= 550 V and
the voltage reserve is 5%, the rms value of the
maximum output voltage in steady-state operation is
0.95 × 550 V / sqrt(2) = 369 V
The dynamic performance of the motor control in the
field weakening area can be improved by increasing
the voltage reserve value, but the drive enters the field
weakening area earlier.
1 = 1 % / 100 = 1 %
Voltage reserve.
-5...50 %
Parameters 527
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...