Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Motor configuration settings.
Motor data
99
Asynchronous motor;
SynRM (95.21 b1);
Selects the motor type.
Note: This parameter cannot be changed while the
drive is running.
Motor type
99.3
Permanent magnet
motor (95.21 b2) /
uint16
0
Standard squirrel cage AC induction motor
(asynchronous induction motor).
Asynchronous motor
1
Permanent magnet motor. Three-phase AC synchronous
motor with permanent magnet motor and sinusoidal
BackEMF voltage.
Permanent magnet
motor
2
Synchronous reluctance motor. Three-phase AC
synchronous motor with salient pole rotor without
permanent magnets.
SynRM
DTC / uint16
Selects the motor control mode.
Note: This parameter cannot be changed while the
drive is running.
Motor control mode
99.4
0
Direct torque control. This mode is suitable for most
applications.
DTC
Note: Instead of direct torque control, scalar control
is also available, and should be used in the following
situations:
•
with multimotor applications
1.
if the load is not equally shared between the
motors,
2.
if the motors are of different sizes, or
3.
if the motors are going to be changed after
the motor identification (ID) run
•
if the nominal current of the motor is less than
1/6 of the nominal output current of the drive
•
if the drive is used with no motor connected (for
example, for test purposes).
See also section
.
536 Parameters
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...