What to do
Cause
Event name /
Aux. code
Code
(hex)
Check the auxiliary code. The code
specifies the I/O port used as follows:
0: Panel, 1: Fieldbus interface A, 2:
Fieldbus interface B, 3: Ethernet, 4:
D2D/EFB port).
See
A799 ExtIO comm loss (page 580)
.
The I/O extension module types
specified by parameters do not match
the detected configuration.
Ext I/O comm
loss
7082
The control panel reference can only
be saved for one reference type at a
time.
Use of saved control panel reference
in multiple control modes attempted.
Panel
reference
conflict
7083
Consider the possibility of using a
copied reference instead of saved
reference (see the reference selection
parameter).
Update control panel and/or PC tool.
The current version of the control
panel and/or PC tool does not support
a function.
Panel/PC tool
version
conflict
7084
Contact your local ABB representative
if necessary.
(For example, older panel versions
cannot be used as a source of external
reference.)
Check the auxiliary code. The code
specifies the interface to which the
unsupported module is connected:
Option module not supported.
(For example, type Fxxx-xx-M fieldbus
adapter modules are not supported.)
Incompatible
option
module
7085
1: Fieldbus interface A, 2: Fieldbus
interface B.
Replace the module with a supported
type.
A - FSO-xx module is not supported by
the control board. Remove FSO-xx
module to clear the fault. Connect
FSO-xx module to the supported
control board.
Check motor load and drive ratings.
Motor is operating in stall region
because of e.g. excessive load or
insufficient motor power.
Motor stall
7121
Check fault function parameters.
Check for overloaded motor.
Motor current is too high.
Motor
overload
7122
Adjust the parameters used for the
motor overload function
…
)
and
…
.
Check that a brake resistor has been
connected.
DC overvoltage detected during
braking.
Brake resistor
7181
Check the condition of the brake
resistor.
Check the dimensioning of the brake
chopper and resistor.
Stop drive. Let resistor cool down.
Brake resistor temperature has
exceeded fault limit defined by
BR excess
temperature
7183
Check resistor overload protection
function settings (parameter group
).
parameter
Check fault limit setting, parameter
43.11 Brake resistor fault limit
564 Fault tracing
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...