What to do
Cause
Event name /
Aux. code
Code
(hex)
Check signal level at the analog input.
Check the wiring connected to the
input.
Check the minimum and maximum
limits of the input in parameter group
.
Check the source of the fault
(parameter
).
Fault generated by the signal
supervision 1 function.
Signal
supervision
80B0
Check the source of the fault
(parameter
).
Fault generated by the signal
supervision 2 function.
Signal
supervision 2
80B1
Check the source of the fault
(parameter
).
Fault generated by the signal
supervision 3 function.
Signal
supervision 3
80B2
Check fan feedback. See parameters
206.30…206.33 for individual failing
fans.
Fan speed is under limit (parameter
206.07).
Fan speed
8E12
See the auxiliary code for incompatible
CIO-01 module. Auxiliary code is a bit
Communication services of the CIO-01
module are incompatible with the
firmware version on the control unit.
I/O module
version
mismatch
8E13
word where bit 0 indicates CIO-01
module assigned to node ID 1.
Replace the incompatible CIO-01
module.
Check miniature circuit breaker and
digital input DI5.
Fault related to miniature circuit
breaker. Some of the bits of the MCB
status word are 0.
CIO MCB
monitoring
8E14
Check fuses and digital input DI6.
Fault related to fuses. Some of the bits
of the fuse status word are 0.
CIO fuse
monitoring
8E15
Check digital input DI8.
Fault related to digital input DI8.
CIO DI8
monitoring
8E17
Check the external device.
Fault in external device 1.
External fault
1
9081
Check setting of parameter
.
Check the external device.
Fault in external device 2.
External fault
2
9082
Check setting of parameter
.
Check the external device.
Fault in external device 3.
External fault
3
9083
Check setting of parameter
.
Check the external device.
Fault in external device 4.
External fault
4
9084
Check setting of parameter
Check the external device.
Fault in external device 5.
External fault
5
9085
Check setting of parameter
.
Informative warning. (See parameter
.)
Current offset and gain measurement
calibration will occur at next start.
Current
calibration
A2A1
Check there are no power factor
correction capacitors or surge
absorbers in motor cable.
Drive has detected load unbalance
typically due to earth fault in motor or
motor cable.
Earth leakage
A2B3
Fault tracing 569
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...