Parameters 259
Selects the optional warning message for signal edge
counter 2.
Edge counter 2
exceeded
. The message text can be edited on
the control panel by choosing Menu – Settings – Edit texts.
3
Counted main
contactor
.
11
Counted output relay
12
Counted motor starts
13
Counted power ups
14
Counted DC charges
.
15
Displays the actual present value of value counter 1.
The value of the source selected by parameter
is read at one-second intervals and
added to the counter. A divisor can be applied to the count
(see
).
When the counter exceeds the limit set by
, bit 4 of
is set
to 1. The warning specified by
The counter can be reset from the Drive composer PC
tool, or from the control panel by keeping Reset depressed
for over 3 seconds.
-
-2147483008
…2147483008
Actual present value of value counter 1.
-
Sets the limit for value counter 1.
With a positive limit, bit 4 of
is set
to 1 (and a warning optionally generated) when the
counter is equal or greater than the limit.
With a negative limit, bit 4 of
is set to
1 (and a warning optionally generated) when the counter is
equal or smaller than the limit.
0 = Counter disabled.
0
-2147483008
…2147483008
Limit for value counter 1.
-
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACS880 PCP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...