Parameters 271
Parameters
…
start/stop control logic for external equipment such as a
contactor-controlled motor cooling fan.
This parameter selects the signal that starts and stops the
fan.
0 = Stop
1 = Start
The output controlling the fan contactor is to be connected
to parameter
, bit 1. On and off delays can be set for
respectively. A feedback
signal from the fan can be connected to an input selected
by
; the loss of the feedback will optionally trigger a
warning or fault (see
).
Off
0 (function disabled).
0
On
1.
1
Running
Bit 6 of
(see page
).
2
Source selection (see
on
page
-
Defines a start delay for the motor fan.
The delay timer starts when the control source selected by
parameter
switches on. After the delay, bit 1 of
switches on.
0 s
0…42949673 s
Motor fan start delay.
1 = 1 s
Defines a stop delay for the motor fan.
The delay timer starts when the control source selected by
parameter
switches off. After the delay, bit 1 of
switches off.
20 min
0…715828 min
Motor fan stop delay.
1 = 1 min
Selects the input for motor fan feedback signal.
0 = Stopped
1 = Running
After the fan is started (bit 1 of
switches on),
feedback is expected within the time set by
.
;
(
b6)
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0). 10
DIO2
Digital input/output DIO2 (
, bit 1). 11
Source selection (see
on page
).
-
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACS880 PCP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...