40.07
IR COMPENSATION
(see above)
Defines the relative output voltage boost at zero speed (IR compensation). The function is useful in
applications with high break-away torque when no DTC motor can be applied.
This parameter is only effective when parameter
is set to
0…50%
IR compensation.
U
/
U
N
(%)
f
(Hz)
Field weakening point
Relative output voltage. No IR
compensation.
Relative output voltage. IR
compensation set to 15%.
15%
100%