Start-up
16
Safety
The start-up may only be carried out by a qualified electrician.
The safety instructions must be followed during the start-up procedure. See the safety
instructions on the first pages of the appropriate hardware manual.
Check the installation. See the installation checklist in the appropriate hardware manual.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine
if
- there is a risk of damage in case of an incorrect direction of rotation, or
- a normal ID run (
) is required during the drive start-up,
when the load torque is higher than 20% or the machinery is not able to withstand the
nominal torque transient during the ID run.
PC tool
Install the DriveStudio PC tool to the PC. For instruction, see
DriveStudio User Manual
[3AFE68749026 (English)].
Connect the drive to the PC:
Connect the other end of the communication cable (OPCA-02, code: 68239745) to the panel
link of the drive. Connect the other end of the communication cable via USB adapter or
directly to the PC serial port.
Power up
Switch the power on.
7-segment display:
Start the DriveStudio program by clicking the DriveStudio icon on the
PC desktop.
Check whether an application program exists using the DriveSPC tool.
If an application program already exists, NOTE that some of the drive
functions may have been disabled. ENSURE, that the application
program is suitable for your drive application.
Switch to local control to ensure that external control is disabled by
clicking the Take/Release button of the PC tool control panel.
->
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Firmware Manual ACSM1 Speed and Torque Control Program...
Page 2: ......
Page 4: ......
Page 12: ...Table of contents 12...
Page 49: ...Drive control and features 49...
Page 282: ...Standard function blocks 282...
Page 306: ...Application program template 306...
Page 312: ...Control chain block diagrams 312...
Page 331: ...331...
Page 332: ...332...
Page 333: ......