Fault tracing
212
0032
OVERSPEED
(0x7310)
Motor is turning faster than
highest allowed speed due to
incorrectly set minimum/
maximum speed, insufficient
braking torque or changes in
load when using torque
reference.
Check minimum/maximum speed settings,
parameters
and
Check adequacy of motor braking torque.
Check applicability of torque control.
Check need for brake chopper and
resistor(s).
0033
BRAKE START TORQUE
(0x7185)
Programmable fault:
Mechanical brake fault. Fault is
activated if required motor
starting torque,
, is not achieved.
Check brake open torque setting, parameter
Check drive torque and current limits. See
parameter group
on page
0034
BRAKE NOT CLOSED
(0x7186)
Programmable fault:
Mechanical brake control fault.
Fault is activated if brake
acknowledgement is not as
expected during brake closing.
Check mechanical brake connection.
Check mechanical brake settings, parameters
.
To determine whether problem is with
acknowledgement signal or brake: Check if
brake is closed or open.
0035
BRAKE NOT OPEN
(0x7187)
Programmable fault:
Mechanical brake control fault.
Fault is activated if brake
acknowledgement is not as
expected during brake opening.
Check mechanical brake connection.
Check mechanical brake settings, parameters
.
To determine whether problem is with
acknowledgement signal or brake: Check if
brake is closed or open.
0036
LOCAL CTRL LOSS
(0x5300)
Programmable fault:
Control panel or PC tool
selected as active control
location for drive has ceased
communicating.
Check PC tool or control panel connection.
Check control panel connector.
Replace control panel in mounting platform.
0037
NVMEMCORRUPTED
(0x6320)
Drive internal fault
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0038
OPTION COMM LOSS
(0x7000)
Communication between drive
and option module (FEN-xx
and/or FIO-xx) is lost.
Check that option modules are properly
connected to Slot 1 and (or) Slot 2.
Check that option modules or Slot 1/2
connectors are not damaged. To determine
whether module or connector is damaged:
Test each module individually in Slot 1 and
Slot 2.
Code
Fault
(fieldbus code)
Cause
What to do
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Firmware Manual ACSM1 Speed and Torque Control Program...
Page 2: ......
Page 4: ......
Page 12: ...Table of contents 12...
Page 49: ...Drive control and features 49...
Page 282: ...Standard function blocks 282...
Page 306: ...Application program template 306...
Page 312: ...Control chain block diagrams 312...
Page 331: ...331...
Page 332: ...332...
Page 333: ......